Boiler Control Instruction & Operation Manual, Rev 1
Page
61
of 64
Specifications
Parameter Summary
Parameter
Range/Choices
Security
Page
MODULATION CONFIGURATION
CH Max Modulation Rate
Minimum to Maximum Modulation
Factory
36
DHW Max Modulation Rate
Minimum to Maximum Modulation
Factory
36
Minimum Modulation Rate
M 100 to Maximum - 100
Factory
36
CH & DHW Forced Rate Time
0 to 30 minutes
Supervisor
36
CH & DHW Forced Rate
1200 to 1300 rpm
Supervisor
36
Stepped Modulation Start Offset
(Stepped Modulation Recycle 6) to 30
Factory
36
Stepped Modulation Recycle Offset
0 to (Stepped Modulation Start Offset - 6)
Factory
37
CH Slow Start Enable/Disable
Enable/Disable
Supervisor
37
DHW Slow Start Enable/Disable
Enable/Disable
Supervisor
37
Slow Start Degrees
0
°
F to 180
Supervisor
37
Slow Start Ramp
0 to 1000 rpm
Supervisor
37
Analog Rate Tracking
Disable / PWM to 4 - 20mA / PWM to 0 - 10V / LL Rate to 4 -
20mA / LL Rate to 0 - 10V
Supervisor
37
Analog Input Hysteresis
0 to 10 tenths
Supervisor
37
Analog Output Hysteresis
0 to 40 tenths
Supervisor
37
PUMP CONFIGURATION
Contact A: CH Pump
Never / Any Demand / Central Heat, No Priority / Central Heat,
Optional Priority / DHW Pump
Supervisor
38
Contact B: Boiler Pump
Never / Any Demand
Supervisor
38
Contact C: DHW Pump
Never / Isolation Valve / DHW Pump
Supervisor
38
Overrun Time: CH Pump (System)
0 to 60 minutes
Supervisor
39
Overrun Time: DHW Pump
0 to 60 minutes
Supervisor
39
Overrun Time: Boiler Pump
0 to 60 minutes
Supervisor
39
Pump Exercise Interval
0 to 40 days
Supervisor
39
Pump Exercise Time
0 to 10 minutes
Supervisor
39
HIGH LIMITS
Preferred Supply High Limit
60 to 200
°
F
Factory
39
STACK LIMIT
Preferred Stack High Limit
150 to 230
°
F
Factory
39
FROST PROTECTION CONFIGURATION
CH Frost Protection
Enable / Disable
Basic
40
CH Frost Protection Setpoint
- 50 to 50 °F
Basic
40
BURNER CONTROL TIMINGS & RATES
Lightoff Rate
Min to Max Lightoff Rate (Model dependent)
Factory
40
SYSTEM CONFIGURATION
Temperature Units
Fahrenheit / Celsius
Basic
40
Antishort Cycle Time
0 to 20 minutes
Basic
40