Boiler Control Instruction & Operation Manual, Rev 1
Page
41
of 64
Setup & Tuning
Parameter Adjustment
Press FAN CONFIGURATION to adjust the following parameters.
Factory
Setting
Range /
Choices
Parameter and Description
500
rpm/sec.
0 to 12000
Fan Speed-Up Ramp
Whenever the burner is firing it will be commanded to increase its RPM no faster
than the rate provided by this parameter. This is a maximum speed limit.
500
rpm/sec.
0 to 12000
Fan Slow-Down Ramp
Whenever the burner is firing it will be commanded to decrease its RPM no faster
than the rate provided by this parameter.
15
1 to 100
Fan Gain Up
This is the gain for speeding up the fan.
8
1 to 100
Fan Gain Down
This is the gain for slowing down the fan.
Press SENSOR CONFIGURATION to adjust the following parameters.
Factory
Setting
Range /
Choices
Parameter and Description
Uncon-
figured
Unconfigured,
S5 (J8-11),
Modbus
Outdoor Temperature Source
Unconfigured Outdoor Sensor is not connected to the boiler, the sensor is not
monitored for faults.
S5 (J8-11) Outdoor Sensor thermistor is installed directly on the boiler PCB-04.
Modbus Outdoor temperature is retrieved through the Modbus connection from
another boiler or Energy Management System.
0°
-50° to 50°
Outdoor Sensor Calibration
Outdoor sensor calibration allows a single point adjustment of the outdoor sensor
reading. This adjustment is a correction offset added to or subtracted from the
outdoor temperature sensor reading. It is recommended to make any calibration
when outdoor air temperature is at or near the most common operating point. For
example, when necessary, calibrate the sensor when outdoor air is halfway
between Minimum and a Maximum Outdoor Temperature parameter value is
recommended.
Press LEAD LAG SLAVE CONFIGURATION to adjust the following parameters.
Factory
Setting
Range /
Choices
Parameter and Description
1
1 to 8
Modbus Address
Each boiler must be given a unique address. When
“Normal” slave selection order is
used, the boiler address is used by the Sequence Master as the boiler start order.
Equalize
run time
Use First,
Equalize run
time,
Use Last
Slave Mode
Use First
Places the Slave in the lead permanently.
Equalize run time
Normal sequence selection order
Use Last
Places the slave last in the firing order.