90
17
Ni1000-LG -60...180 ºC
18
Cu100 -50...180 ºC
19
Voltage -5...20mV
20
Voltage -75...75mV
21
Voltage -200...200mV
22
Thermocouple J 0...400ºC
23
Thermocouple J -200...1200ºC
24
Thermocouple K 0...400ºC
25
Thermocouple K -200...1370ºC
26
Thermocouple S 0...1760ºC
27
Thermocouple N -20...420ºC
28
Thermocouple N -200...1300ºC
29
Thermocouple E -40...260ºC
30
Thermocouple E -200...1000ºC
31
Thermocouple R 0...1760ºC
32
Thermocouple T -200...400ºC
33
Thermocouple B 400...1800ºC
34
RS-485 mode
4001
AvgTime
w/
r
75...20000
1000
Averaging time of the measured value [ms]
4002
Point No
w/
r
1...21
1
Number of individual characteristics pointst.
For the value of 1 individual characteristic is
switched off. Sections of individual characte
-
ristic are defined with Xn and Yn parameters,
where n – point number.
4003
Compens.
w/
r
0...1
1
Compensation type of:
- cold junction temperature for thermocouples
- cords resistance for measuring resistance
and temperature from thermistor sensors
Value
Description
1
Automatic compensation
0
Manual compensation (compensation
value should be written into 7668 register)