Page 46
Selecting the output status if normally open or closed: [1411]
n. oPEn. Relay 2 is normally open. [0]
n.CLoSE Relay 2 is normally closed. [1]
Defaul: n. oPEn.
Select if positive or negative values have to be compared. [1412]
PoSIt..
The output is operative with positive weight. [0]
nEGAt.
The output is operative with negative weight. [1]
ALL:
The output is operative both with positive and negative weight. [2]
Default: PoSIt
Select whether only stable weight values are to be compared or also unstable: [1413]
norMAL Output 2 is active with unstable weight. [0]
StAbLE
Output 2 is active with stable weight. [1]
Default: norMAL
HySt. 2
SET-POINT 2 HYSTERESIS [1414]
Hysteresis value with respect to the set-point
Value: from 0 to Capacity
Default: 2
t1NEr2
SET-POINT 2 TIMING [1415]
Value of time, in tenths of a second, during which, when the weight value set is exceeded, the output
associated with set-point 2 remains enabled.
After this time, even if the weight value is still above the set-point, theoutput is automatically disabled.
The function is not active with programmed time equal to zero.
Values: from 000 to 999
Default: 0
dELAy2
SET-POINT 2 DELAY [1416]
Value of time, in tenths of a second, after which, when the set weight value is exceeded, the output
associated with set-point 2 is enabled.
The function is not active with programmed time equal to zero
Values: from 000 to 999
Default: 0