Page 70
77-78
38
Input 1 mode —Logic
See correspondence on page 45
79-80
39
Input 1 mode —Polarity
See correspondence on page 45
81-82
40
Input 1 mode —Stability
See correspondence on page 45
83-84
41
Hysteresis input 1
INT. value
85-86
42
Timing input 1
INT. value
87-88
43
Delay input 1
INT. value
89-90
44
Input 2 mode —Function
See correspondence on page 45
91-92
45
Input 2 mode —Logic
See correspondence on page 46
93-94
46
Input 2 mode —Polarity
See correspondence on page 46
95-96
47
Input 2 mode —Stability
See correspondence on page 46
97-98
48
Hysteresis input 2
INT. value
99-100
49
Timing input 2
INT. value
101-102 50
Delay input 2
INT. value
103-104 51
Analogue Fixed Tare (MSB)
INT. value - Most significant word
105-106 52
Analogue Fixed Tare (LSB)
INT. value - Less significant word
107-108 53
Analogue Full Scale (MSB)
INT. value - Most significant word
109-110 54
Analogue Full Scale (LSB)
INT. value - Less significant word
111-112 55
Analogue Output Mode
See correspondence on page 32
113-114 56
Analogue Output Range
See correspondence on page 32
(*) These registers can only be modified in FREE mode or if in METRIC mode with a calibration
bridge enabled.
WRITING EXAMPLES
To write the set-up parameters following the example:
In the bytes 1-2 (Command Register) write value Hex 3FFF. This value opens the writing area of the
DAT 11.
Example: to change the default values of the DAT 11 like the Capacity of the load cells, the Sensitivity
and Division value to 15000, 2.9965 and 2:
Capacity
Byte 17
Byte 18
Byte 19
Byte 20
Hex
00
00
3A
98
Dec
15000
Sensitivity
Byte 21
Byte 22
Hex
75
0D
Dec
29965
Division
Byte 23
Byte 24
Hex
00
0D
Dec
13
Save the data by writing the value Hex 7 in Command Register.
N.B. The DAT 11 does not accept writing of the same values already written.
To perform Zero and FS Calibration it is not needed to abilitate the internal Writing Area of the DAT 11.
Zero Calibration:
Whit empty system put Hex 4 in Command Register (bytes 1-2). The new Zero value is stored.
Full Scale Calibration:
Put a know weight on the system and write its value in the Data Register (from byte 3 to 6). Put value
Hex 5 in Command Register. The weight value will be displayed.
Содержание DAT11
Страница 2: ...Page II ...
Страница 83: ...Page 81 ...