![Paul NOVUS 300 Скачать руководство пользователя страница 45](http://html2.mh-extra.com/html/paul/novus-300/novus-300_original-operating-instructions_4024729045.webp)
45
Menu settings by qualified personnel / service staff
3.6
The password-protected parameters may only be changed by a competent expert or service
staff!
Main menu Setup
3.6.1
The main menu
Setup
is divided in eight submenus. The access to the submenus is password-protected.
Symbol
Designation
Explanation / actions
Button
Menu mode
By touching the button Menu mode, you reach the main menus.
Buttons
Navigation
By touching the navigation buttons, select the main menu setup
and confirm with Enter.
Button
Password
Password prompt
Enter the password _ _ _ _ _ and confirm with Enter.
Buttons
Navigation
By touching the navigation buttons, select the respective submenu
and confirm with Enter.
Tab. 30: Sequence of steps access main menu setup
The settings in the submenu are only applied if Enter is touched!
3.6.1.1 Submenu Frost protection
The following settings are made in the submenu Frost protection:
•
Parameterisation of the temperatures, () values factory setting:
o
Anti-freeze protection threshold intake air eco (-2.0 °C)
o
Anti-freeze protection threshold intake air safe (0.0 °C)
o
Anti-freeze protection threshold intake air moisture heat exchanger (-8.0 °C)
o
Anti-freeze protection threshold minimum supply air temperature (5.0 °C)
•
Selection of the type of defroster heater
o
Electric
defroster
o
PTC defroster
o
Brine
defroster
Symbol
Designation
Explanation / actions
Buttons
Navigation
Temperatures
Select by touching the navigation buttons (red background of the
text) and confirm with Enter.
Buttons
Navigation
Anti-freeze protection thresholds
Using the navigation buttons, the characteristic variables (red
background of the text) to be parameterised can be selected and
the values can be set using the b / -.
Buttons
Enter
Cancel / back
Confirm by touching the Enter button. By touching the Cancel /
back button, exit the menu level.
Содержание NOVUS 300
Страница 1: ...Version 2 0_10 2014 EN...
Страница 59: ...59 Dimensional sketch 3 9 5 Fig 47 Dimension drawing HRU NOVUS...
Страница 60: ...60 Plant 1 circuit diagram NOVUS 3 9 6...
Страница 61: ...61 Plant 2 circuit diagram NOVUS with integrated defroster 3 9 7...
Страница 62: ...62 Plant 3 Terminal scheme of through terminal X10 3 9 8...