44
Fig 41: Chart 2, setting values nominal air flow NOVUS (F) 450 with fan speed 2 (FS2)
3.5.2.2 Adjustment of the nominal air flow with LED control panel
For adjusting the ventilation plant, the speed of the LED control panel which corresponds to the settings
of set value. The seven steps of the LED control panel are factory-set values of the fans according to tab.
14. Correspond to the adjusted level for the nominal air flow rate has the nearest set value from chart 1,
Fig 40 or chart 2 Fig 41. During the adjustment of the valves, this fan speed is maintained.
Fan speed
level
LED control
panel
Setting of set value [%]
Version LEFT
Setting of set value [%]
Version LEFT
NOVUS (F) 300
NOVUS (F) 450
NOVUS (F) 300
NOVUS (F) 450
1
17
25
17
20
2
29
39
29
32
3
41
50
44
43
4
53
61
57
53
5
65
74
70
65
6
74
84
81
74
7
100
100
100
100
Tab. 29: Setting values nominal air volume flow
Adjustment of the Valves
3.5.3
Make sure that the supply and extract air valves are open as much as possible at the
beginning of the volume flow measurement.
•
Set the fans to nominal air volume flow.
•
Adjustment of the air volume flows to the air valves by means of a volume flow hood and an
anemometer (see air volume log)
•
Adjustment of the air gap on the valve must not be too narrow – aerodynamic noises! Better:
Adjustment of a lower fan output or restriction of the volume flow in the pipeline (installation of a
throttle flap or throttle foam insert)
•
Readjustment of the valves
•
Locking of the adjusted positions of the valves and flaps
•
Recording of the adjusted air quantity and all further adjustments in the designated documentations
Содержание NOVUS 300
Страница 1: ...Version 2 0_10 2014 EN...
Страница 59: ...59 Dimensional sketch 3 9 5 Fig 47 Dimension drawing HRU NOVUS...
Страница 60: ...60 Plant 1 circuit diagram NOVUS 3 9 6...
Страница 61: ...61 Plant 2 circuit diagram NOVUS with integrated defroster 3 9 7...
Страница 62: ...62 Plant 3 Terminal scheme of through terminal X10 3 9 8...