13
LED L8
LED L11
LED L10
LED L12
LED L9
LED L1 … L7
…
…
Key combination
configuration mode
upper temperature
threshold of by-pass
Keys for setting upper
temperature threshold
of by-pass
By pressing the key combination for at least 3 s, the
configuration mode upper temperature threshold of By-
pass is activated and the LEDs L8 and L10 are blinking.
By means of the keys, only the upper temperature
threshold for the opening of the by-pass can be adjusted in
dependency on the extract air temperature between 21°C
(LED L1) and 27°C (LED L7). The lower threshold has a
fixed pre-set value of 18°C. After the repeated actuation of
the key combination for at least 3 sec, the setting is applied
and the configuration mode upper temperature threshold of
by-pass is closed.
…
…
Key combination
configuration mode
imbalance
Keys for balance setting
By pressing the key combination for at least 3 s, the
configuration mode imbalance is activated and the LEDs
L10 and L12 are blinking. By means of the keys for balance
setting, the balance of the fan speed which was active
during the activation of the configuration mode imbalance
can now be adjusted in steps of 5 %. The balance setting is
not carried out separately for each fan speed, but jointly for
groups of fan speeds.
The adjustable range is from -15 % (L1) to + 15 % (L7). In
centre position (L4), the supply and extract air fans run at
the same rotation speed. After having actuated the key
combination once again, the setting is accepted and the
configuration mode imbalance is terminated.
The key Reset filter change must always be
pressed in the first place!
1. Group
fan speeds <1+2>
2. Group
fan speeds <3+4+5>
3. Group
fan speeds <6+7>
Tab. 2: Operating functions of the LED control panel
2.2.1.2 Signalling of operating and error conditions
LED signalling
Function / meaning
LED lamp display
L1 ... L7
No LED
ԑ
fan speed 0 (fan off, standby)
1 LED (L1)
ԑ
fan speed 1
2 LEDs (L1 + L2)
ԑ
fan speed 2
... etc.
7 LEDs (L1 + L2 + … + L7)
ԑ
fan speed 7
L1 + L7 are lit
No external release: fan off
Fig 6: LED signalling of the LED control panel
Содержание NOVUS 300
Страница 1: ...Version 2 0_10 2014 EN...
Страница 59: ...59 Dimensional sketch 3 9 5 Fig 47 Dimension drawing HRU NOVUS...
Страница 60: ...60 Plant 1 circuit diagram NOVUS 3 9 6...
Страница 61: ...61 Plant 2 circuit diagram NOVUS with integrated defroster 3 9 7...
Страница 62: ...62 Plant 3 Terminal scheme of through terminal X10 3 9 8...