41
System Manual | 2014
PA8500-VES System
UK
CR8506-V
|
RT8506-V
8.4.1
FAULTS
For viewing the failed components
Six.groups.are.listed,.with.a.generic.indication.of.the.fault.condition.
The.categories.of.failed.parts.and.generic.signalling.of.their.states.are.shown.in.the.
table.below.
Press.the.associated.numerical.key.(
1-6
).to.select.the.sub-panel.and.view.the.details.
of.the.failure,.as.illustrated.under.points.below
or.
Press.ESC.to.return.to.the.INSPECTION.panel.
8.4.1.1 Automatic resetting of the acoustic signal (beep) following clearing of a failure
If.the.cause.of.a.failure.is.cleared.before.the.beep.is.reset.manually.(see.OPERATOR.Menu,.point.8.5.3.1,.page.51),.the.CR8506-V.will.reset.
the.beep.automatically,.extinguish.the.FAULT.LED.and.indicate.RES.(RESUMED).in.the.label.of.the.part.that.had.FAILED..The.RESOLVED.
signal.will.be.stored.until.a.MANUAL.RESET.of.the.failure.signal.is.carried.out.from.the.FAULTS.panel.via.the.OPERATOR.menu.
Tab..8.4.1.1
Label
Diagnostic category
See panel
Signalling Cause
1-Loudspk.Line
Loudspeaker.lines
LOUDSPk..LINE.FAULT
ALL
Ok
No.faults
2-Voice.Alarms
VES.emergency.sources
VOICE.ALARMS.FAULT
3-Amplifiers
Power.amplifiers.
Ground.fault.loudspeaker.lines
AMPLIFIER.FAULTS
4-Power.Supply
Primary.and.secondary.power.supplies.
Management.memory.display
POWER.SUPPLY.FAULTS
FAULT
At.least.1.fault.detected..
and.on-going.
5-Control.Input
Local.input.contacts
CONTROL.INPUT.FAULT
RES
At.least.1.fault.cleared..
and.no.on-going.faults
6-Communication CR8506-V.internal.data.
communication
COMMUNICATION.FAULT