55
System Manual | 2014
PA8500-VES System
UK
CR8506-V
|
RT8506-V
8.6.4
ALARM LEVEL
Adjustment of the volume of VES sources
Panel.for.adjusting.the.output.volume.of.VES.sources.for.the.purpose.of.calibrating.
the.system..
To.adjust.the.volume.of.the.required.source:.
•.hold.the.corresponding.numbered.key.(1.-.5).down.
..
and
•.use.the.+/-.knob.to.adjust.the.volume.
Note:.The.volume.set.will.be.the.same.for.all.the.output.zones.
Upon.completion,.press.ESC.to.return.to.the.CONFIGURATION.menu.
1-Output volumes of the PMB132 emergency microphone stations connected to their local CR8506-V unit:
the. adjustment. range. for. the.
EMERGENCY.UNITS.is.between.-80.dB.and.0.dB.
2-Output volume of hand-held emergency microphones:
the. adjustment. range. for. FIRE. MICROPHONES. is. between. -80. dB. and. 0. dB..
It.is.suggested.that.in.most.cases.a.volume.of.+16.dB.should.not.be.exceeded.
3-Output volume of pre-recorded ALERT messages:
.the.adjustment.range.for.ALERT.MESSAGES.is.between.-80.dB.and.0.dB.
4-Output volume of pre-recorded EVACUATION messages:
The.adjustment.range.for.EVAC.MESSAGES.is.between.-80.dB.e.0.dB.
5-Volume of emergency signals from CR8506-V remote controllers:
.the.adjustment.range.for.CR8506-V.LINk.is.between.-80.dB.e.0.dB.
8.6.5
AMPLIFIER TEST TIME
Setting the interval between test signals for testing amplifiers of the
PMD range
•.Hold.the.corresponding.numerical.key.(1.to.3).down.and.use.the.+/-.knob.to.adjust.
the.setting:
1-Line. Line.
.(1.to.6)
2-Amp. Amplifier.
(1.to.16./.ALL)
3-Time. Length.of.test.
(5s.to.18h./.no.test).
Upon.completion,.press.ESC.to.return.to.the.CONFIGURATION.menu.
.
8.6.6
DISABLEMENT
.
Disabling the emergency zones
Panel.for.setting.the.“Disablement.Condition”.for.each.output.zone.
•.Press.the.numerical.key.corresponding.to.the.line.(1.to.6).
then
•.Press.the.appropriate.zone.key.to.enable.or.disable.it.
Application. of. the. “Disablement. Condition”. refers. to. the. functions.
envisaged. for. a. “Voice.Alarm. Condition”,. and. does. not. affect. the.
system. in. terms. of. its. usual. activities. in. a. “quiescent. Condition”..
Thus,. if. “Disablement”. is. set. for. at. least. one. output. zone,. the.
dedicated.“DIS”.LED.will.in.any.case.light.up.to.show.that.there.is.a.
generic.“Disablement.Condition”.within.the.system.
The.status.label.of.each.zone.will.signal.a.possible.“Disablement.Condition”.set.with.a.priority.higher.than.the.signals.called.for.by.a.“Voice.Alarm.
Condition”.and.a.“Fault.Warning.Condition”..During.a.Manual.Emergency.procedure,.it.will.not.be.possible.to.select.the.disabled.zone.for.sending.
alarm.messages..For.details.consult.point.8.8.
The.zone.in.a.“Disablement.Condition”.will.not.be.affected.by.voice.
or.pre-recorded.emergency.messages,.regardless.of.how.the.input.
contacts. (CONTROL. INPUTS). are. programmed. and. of. how. the.
Operator. proceeds. during. a. Manual. Emergency. procedure.. . The.
“disabled”. zone. will. therefore. not. be. affected. by. a. “Voice. Alarm.
Condition”.of.the.system..