53
System Manual | 2014
PA8500-VES System
UK
CR8506-V
|
RT8506-V
8.6.1
ACQUIRE IMPEDANCE
Line impedance acquisition
Panel. for. acquiring. and. storing. the. impedance. levels. of. the. speaker. unit.
lines..This.information.is.necessary.for.system.initialisation.and.diagnostics.
8.6.1.1 Loudspeaker line impedance acquisition
Foreword
Before.acquiring.the.impedance.values,.make.sure.that.the.following.steps.
have.been.completed:
•. Preliminary.check.of.the.impedance.of.the.lines.using.a.suitable.instrument.
(IMPEDANCE-METER).and.of.the.loading.conditions.
•. Connection.of.the.speaker.unit.lines.as.indicated.in.the.CONNECTIONS.
Section.
The.new.impedance.values.acquired.will.be.stored.automatically.in.the.system.and.shown.on.the.labels.of.each.zone..They.are.in.Ohms.and.refer.
to.both.lines,.A.and.B,.connected.to.the.output.of.each.zone..The.impedance.values.residing.in.the.memory.will.be.compared.by.the.monitoring.
system.with.the.values.measured.subsequently.during.the.diagnostics.routine.
Note:
To.measure.the.impedance.of.the.speaker.unit.lines,.the.monitoring.system.provided.in.the.CR8506-V.uses.an.inaudible.20.kHz.tone..Due.to.the.
inductance.of.the.loudspeaker.coils,.the.impedance.at.20.kHz.may.be.considerably.different.from.that.measured.with.an.impedance.meter,.which.usually.
uses.a.1.kHz.measuring.tone..The.value.acquired.by.the.CR8506-V.is.therefore.usually.indicative.only.as.a.comparative.value.for.diagnostic.purposes..
For.this.reason,.when.calculating.the.power.absorbed.by.the.speaker.unit.lines.for.the.purpose.of.sizing.the.system.it.is.recommended.to.use.the.value.
measured.with.an.impedance.meter.
* The amplifiers of the PMD range use a tone that has a frequency of 30 Hz.
Press.ESC.to.return.to.the.CONFIGURATION.menu.
Upon.completing.the.procedure,.carry.out.a.MANUAL.RESET.of.the.FAILURE.SIGNALLING,.as.described.under.point.8.5.3.1,.page.51.
After.selecting.“Acquire>.IMPEDANCE”.from.the.CONFIGURATION.menu,.the.“ACqUIRE.IMPEDANCE”.panel.will.show.the.impedance.values.
stored.at.the.time.of.the.previous.acquisition:
....
.
•.
press the OK key
8.6.2
SET TOLERANCE
Setting the line tolerance
If. the. diagnostic. system. detects. a. difference. between. the. impedance.
measured. in. real. time. and. the. value. stored. in. the. system. greater. than.
the.tolerance.that.was.set:.an.“Impedance.Low”.or.“Impedance.Hi”.“Fault.
Warning.Condition”.will.be.activated..For.details.about.signalling.of.failures,.
see.the.“LOUDSPk..LINE.FAULT”.panel..(point.8.4.1.2,.page.42).
8.6.2.1 Setting the tolerance for measuring the lines
Foreword:. The. measurement. tolerance. must. be. set. after. completing.
acquisition.of.the.line.impedance
(see point 8.6.1).
The.default.value.is.30%.
.
•.press.the.numerical.key.corresponding.to.the.line..
.
•.Hold.the.numerical.key.corresponding.to.the.zone.(1-6).down,..
.
..turning.the.+/-.knob.to.choose.the.required.value.
>Valori da 10% a 100%:
tolerance.above.or.below.the.stored.value.
>Test Disabled:
Impedance.check.disabled..Testing.for.short.circuits.and.
GND.faults.will.in.any.case.be.carried.out.
It.is.also.possible.to.disable.the.impedance.test.by.setting.a.tolerance.of.
0%.(Not.Tested).
Press.ESC.to.return.to.the.CONFIGURATION.menu.
Upon.completion.of.the.procedure,.if.appropriate.carry.out.a.MANUAL.
RESET.OF.THE.FAILURE.SIGNALLING.as.described.under.point.
8.5.3.1,
page 51.
After.selecting.the.“Set>.IMP..TOLERANCE”.option.from.the.CONFIGURATION.
menu,.the.“SET.TOLERANCE”.panel.will.show.the.current.tolerance.settings.
for.each.output.zone.
Содержание CR8506-V
Страница 2: ......
Страница 9: ... System Manual 2014 PA8500 VES System UK CR8506 V RT8506 V 4 CONNECTIONS ...
Страница 62: ......
Страница 63: ......