13
System Manual | 2014
PA8500-VES System
UK
CR8506-V
|
RT8506-V
D2) Various types of PA source with progressive degrees of priority, “voice” amplification channel
Connection.by.way.of.example.of.one.table-top.microphone.station,.not..pre-amplified,.with.a.precedence.contact;.of.one.grip-type.microphone.
with.automatic.VOX.activation.over.music;.of.one.PABX.with.an.audio.output.for.automatic.announcements.over.the.sound-broadcasting.system.
and.digital.stations.of.the.PMB.range.for.service.announcements.with.zone.selection..For.details.concerning.the.settings.refer.to.the.relevant.
sections.indicated.under.AUDIO.SETTING.
A
.-.Table-top.base.with.electret.microphone,.balanced.output.connected.to.the.
IN.1.input.–.MIC.and.precedence.contact.connected.to.the.PPREC..input.
The.announcement.will.be.addressed.to.the.group.of.zones.indicated.in.the.
ZONE.LIST.on.the.basis.of.the.priority.set.
Set.the.via.the.INPUT.1.panel:. >MODE:.PRECEDENCE
.
.
>PH:.ON
.
.
>Priority:.3.
.
.
>Zone.list:.as.desired
.
.
>VOL.:.as.desired
Set.the.via.the.CHIME.panel:.
>.MIC.1:.ON..
B
.-.Grip-type.dynamic.microphone,.balanced.output.connected.to.the.input.
IN.2–.MIC.with.VOX.function.
The.announcement.will.be.addressed.to.the.group.of.zones.indicated.on.the.
ZONE.LIST.according.to.the.priority.that.is.set.
Set.the.via.the.INPUT.2.panel:. >MODE:.VOX
.
.
>PH:.OFF
.
.
>Priority:.1.
.
.
>Zone.list:.as.desired
.
.
>VOL.:.as.desired
Set.the.via.the.CHIME.panel:.
>.MIC.2:.OFF.
Caution! Do not connect any other equipment to the LINE terminals
of the IN.2 input.
C
.-.Digital.microphone.stations.connected.in.cascade.formation.to.the.PAGING.
UNIT.input..The.announcement.will.be.addressed.to.the.zones.indicated.when.
programming.the.keys.of.the.bases.depending.on.the.priority.set.for.each.
base.
Set.the.PAGING.UNITS.panel:
.
.
>VOL.:.as.desired.(volume.of.the.whole.line.
.
.
.
.for.all.the.bases)
Set.the.CHIME.panel:.
>.UNIT:.ON
Sizing
:.For.each.CR8506-V.unit,.up.to.a.maximum.of.16.stations.of.the.PAGING.UNITS.range.can.be.connected..Use.the.Cat..5.SF/UTP.connecting.
cable,.with.its.shielding.plait..The.following.limits.must.be.observed.for.the.connections:
N..1.station.connected.to.a.line.800.metres.long.
N..8.stations.distributed.along.2.lines,.each.200.metres.long.(4.stations.per.line).
For.systems.calling.for.greater.distances.or.a.higher.number.of.stations.to.be.connected,.it.is.advisable.to.power.the.stations.by.means.of.the.additional.
power.supply.unit.connected.to.the.local.socket.of.the.base..The.maximum.length.of.the.connecting.line,.adding.up.the.lines.connected.to.the.two.RJ45.
sockets,.is.1.km..For.further.details.concerning.the.type.of.power.supply,.the.configuration.of.the.cable,.programming.of.the.selection.keys.and.setting.
of.the.priorities.and.addresses,.refer.to.the.Instruction.Manual.of.the.stations.of.the.PMB.range.
The.following.PAGING.UNITS.can.be.connected.to.the.
CR8506-V
:
•.
PMB106-G
:.
6
-zone.paging.unit.
•.
PMB112-G
:.
12
-zone.paging.unit.
N.B.: The connections between the CR8506-V and PAGING UNITS must be made solely with CAT. 5e SF/UTP.
.