P
AGE
30
STEP
DESCRIPION
DISPLAY
AVAILABLE
FACTORY YOUR
CODE
SETTINGS
SETTING
SETTING
6
Output 2
out2
0 = None or Position
0
Proportioning Direct -Close
1 = On-Off Direct (Cooling)
2 = On-Off Reverse (Heating)
3 = Time Proportioning-
Direct (Cooling)
4 = Time Proportioning-Reverse
(Heating)
5 = Current Proportioning-
Direct (Cooling)
6 = Current Proportioning-
Reverse (Heating)
7 = Position Proportioning
Reverse -Close
7
Output 2 %
o2uL
1 to 100%
100
Upper Limit
(o2uL and o2LL will
be displayed if out2
is selected as 3,4,5,6)
8
Output 2 %
o2LL
0 to 100%
0
Lower Limit
9
Output 3
out3
0 = None
0
1 = Process Alarm-Direct
2 = Process Alarm-Reverse
3 = Deviation Alarm-Direct
4 = Deviation Alarm-Reverse
5 = Deviation Band Alarm-
Open within band
6 = Deviation Band Alarm-
Closed within band
10
Relay A
rLyA
0 = Not assigned
1
Assignment
1 = Assigned to Output 1
2 = Assigned to Output 2
3 = Assigned to Output 3
11
Relay B
rLyb
Same selection as Relay A
2
Assignment
(rLyb will be
displayed if the relay
is specified at the
time of order)
12
Relay C
rLyC
Same selection as Relay A
3
Assignment
(rLyC will be
displayed if the relay
is specified at the
time of order)
13
Upper Display
diSP
1 = Process Value (PV)
1
Select
2 = Deviation
14
Decimal Position
dPoS
0 or 1 for T/C and RTD Input
0
0 to 3 for volt/mV Input
15
Engineering units
Euu
-9999 to 9999
1000
Upper Value
(Euu and EuL will
be displayed if inPS=
30, 31, 32, 33, 34)