† Sets scale of remote signal.
# Both Local & Remote Limits
STEP
DESCRIPION
DISPLAY
AVAILABLE
FACTORY
YOUR
CODE
SETTINGS
SETTING
SETTING
16
Engineering units
EuL
-9999 to 9999
0
Lower Value
17
Hysteresis for
HyCo
0 to 300
°
/Units
3
On/Off Control
(width of hysteresis band)
Output(s)
18
Hysteresis for
HyAo
0 to 300
°
/Units
3
Alarm Output
(width of hysteresis band)
19
Setpoint
SPC
0 to 4
0
Configuration
0 = Single Local Setpoint
**1 = 1 to 5VDC Remote
Setpoint and Single Local
Setpoint
**2 = 0 to 5VDC Remote
Setpoint and Single Local
Setpoint
3 = Dual Local Setpoint -
keypad selectable
**4 = Dual Local Setpoint -
Remote Dry Contact
Closure Selectable
**These features can be selected in the setpoint
configuration but will not function unless the Remote
Setpoint option is present, model #82XXX2X.
20
Remote Setpoint
rSPu†
-9999
°
to 9999
°
/Units
1400*
Upper Limit
(rSPu and rSPL will
be displayed if SPC is
selected as 1 or 2 and
model #82XXX2X has
been selected)
21
Remote Setpoint
rSPL†
-9999
°
to 9999
°
/Units
0*
Lower Limit
22
Setpoint
SPuL#
-9999
°
to 9999
°
/Units
1400*
Upper Limit
23
Setpoint
SPLL#
-9999
°
to 9999
°
/Units
0
Lower Limit
24
Automatic Transfer AtFr
0 = No automatic transfer
0
1 = Transfer when PV
goes below setpoint
2 = Transfer when PV
goes above setpoint
25
Process
PFF
1 to 20 (# of scans averaged)
1
Filter Factor
1 = no filtering
26
Display
dFF
1 to 20 (# of scans averaged)
1
Filter Factor
1 = No Filtering
27
Fast Scan
FSCn
0 or 1
0
0 = Standard Scan -
1 per second
1 = Fast Scan -
3 per second