RELAY A
115
230
VAC
CJC
SIGNAL -
MADE IN U.S.A
GROUND
INPUT RATINGS:
115/230 VAC 50/60 HZ 15VA MAX
RELAY OUTPUT RATINGS:
115VAC 5.0A RESISTIVE
230VAC 2.5A RESISTIVE
230VAC 1/8 HP
115/230VAC 250VA
MAXIMUM AMBIENT : 55
°
C
5
6
8
7
E
F
G
H
RETURN
OUT1
4-20mA
+
OUT2
4-20mA
+
REMOTE
SETPT
+
SERIAL A
SERIAL B
POS.PROP.
WIPER
POS.PROP.
HIGH
RELAY C
RELAY B
CJC
(Continued from page 11)
Example:
An application uses 2000 feet of 18 AWG copper lead wire for a 3 wire RTD sensor. What is
the worst case error due to this leadwire length?
Terr = TLe * L
TLe = +/-.46 (
°
F/1000 ft) from Table 3
Terr = +/-.46 (
°
F/1000 ft) * 2000 ft
Terr = +/- 0.92
°
F
FIGURE 2-4 WIRING LABEL