All-in-one solar charge inverter V11 11
2.2 Wiring specifications and circuit breaker selection
Wiring and installation must comply with national and local electrical codes.
Recommended PV array wiring specifications and circuit breaker selection: Since the output current of
the PV array is affected by the type, connection method and illumination angle of the PV module, the
minimum wire diameter of the PV array is calculated according to its short-circuit current; refer to the
short-circuit current value in the PV module specification (the short-circuit current is constant when the
PV modules are connected in series; the short-circuit current is the sum of the short-circuit currents of
all PV modules connected in parallel); the short-circuit current of the PV array shall not exceed the
maximum input current.
Refer to the table below for PV input wire diameter and switch:
Models
Recommended PV
wiring diameter
Maximum PV
input current
Recommended air switch or
circuit breaker type
HF4830S60-145
10mm
2
/7AWG
40A
2P—63A
HF4840S80-145
10mm
2
/7AWG
50A
2P—63A
HF4850S80-145
10mm
2
/7AWG
50A
2P—63A
Note:
The voltage in series shall not exceed the maximum PV input open circuit voltage.
Refer to the table below for recommended AC input wire diameter and switch:
Models
Recommended AC
input wiring diameter
Maximum
bypass input
current
Recommended air switch or
circuit breaker type
HF4830S60-145
10mm
2
/7AWG
30A
2P—40A
HF4840S80-145
10mm
2
/7AWG
40A
2P—40A
HF4850S80-145
10mm
2
/7AWG
40A
2P—40A
Note:
There is already an appropriate circuit breaker at the Mains input wiring terminal, so it is
not necessary to add one more.