background image

 

All-in-one solar charge inverter    V11                                                                                                                                                               32 

5. Other functions 

5.1 Dry node 

Working principle: This dry node can control the ON/OFF of the diesel generator to 

charge the battery.  ① Normally, the terminals are that the NC-N point is closed and 

the NO-N point is open; ② When the battery voltage reaches the low voltage 

disconnection point, the relay coil is energized, and the terminals turn to that the  

NO-N point is closed while NC-N point is open. At this point, NO-N point can drive 

resistive loads: 125VAC/1A, 230VAC/1A, 30VDC/1A. 

 

5.2 RS485 communication port

 

This port is an RS485 communication port ;  

This port is an RS485-2 communication port is an optional function, which is not available in the 

standard machine. 

This port is an RS485-1 communication port which comes with two functions: 

①  It allows direct communication with the optional host computer developed by our 
company through this port, and enables monitoring of the equipment running status 
and setting of some parameters  on the computer;  
②   It  also  allows  direct  connection  with  the  optional  RS485  to  WiFi/GPRS  
communication  module  developed  by  our  company  through  this  port.  After  the 
module is selected, you can connect the all-in-one solar charge inverter through the 
mobile phone WiFi/GPRS APP, on which you can view the operating parameters and 
status of the device. 
  

As shown in the figure:

  

Pin 1 is 5V power supply, Pin 2 is GND, Pin 7 is RS485-A, and Pin 8 is RS485-B ; 

 
5.3 USB communication port 

This is a USB communication port, which can be used for USB communication with 

the optional PC host software. To use this port, you should install the corresponding 

"USB to serial chip CH340T driver" in the computer. 

 

 

Содержание HF4830S60-145

Страница 1: ...All in one solar charge inverter V11 1 All in one solar charger inverter User Manual Product models HF4830S60 145 HF4840S80 145 HF4850S80 145...

Страница 2: ...lammable or explosive or heavily dusty areas The mains input and AC output are high voltage so please do not touch the wiring terminals The housing of the all in one solar charge inverter is hot when...

Страница 3: ...11 2 3 INSTALLATION AND WIRING 13 3 OPERATING MODES 19 3 1 CHARGING MODE 19 3 2 OUTPUT MODE 20 4 LCD SCREEN OPERATING INSTRUCTIONS 21 4 1 OPERATION AND DISPLAY PANEL 21 4 2 SETUP PARAMETERS DESCRIPTI...

Страница 4: ...loys advanced SPWM technology and outputs pure sine wave to convert DC into AC It is ideal for AC loads such as household appliances power tools industrial equipment and electronic audio and video equ...

Страница 5: ...t to power the load while charging the battery If the mains or generator is not connected the system can also operate normally and the load is powered by the battery and PV module 3 Battery Provided t...

Страница 6: ...145 AC input port Cooling fan AC output port Battery port CAN communication port ON OFF rocker switch USB communication port PV port RS485 communication port Touch button Dry contact port LED Indicat...

Страница 7: ...ector Dry contact port ON OFF rocker switch Cooling fan AC input port Battery port AC output port Cooling fan Grounding screw hold PV port RS485 2 communication port Touch the key lightly USB communic...

Страница 8: ...All in one solar charge inverter V11 8 1 4 Dimension drawing HF4830S60 145...

Страница 9: ...All in one solar charge inverter V11 9 Other models...

Страница 10: ...have been tightened and the wires are secured with ties to avoid looseness of connections caused by shaking of wires during mobile application The system connection wires are selected according to a c...

Страница 11: ...connected in parallel the short circuit current of the PV array shall not exceed the maximum input current Refer to the table below for PV input wire diameter and switch Models Recommended PV wiring d...

Страница 12: ...d inverter AC output current Maximum bypass output current Recommended air switch or circuit breaker type HF4830S60 145 10mm2 7AWG 13A 30A 2P 40A HF4840S80 145 10mm2 7AWG 17 5A 40A 2P 40A HF4850S80 14...

Страница 13: ...one solar charge inverter ensure that there is enough air flowing through the heat sink and space of at least 200m to the left and right air outlets of the inverter shall be left to ensure natural co...

Страница 14: ...All in one solar charge inverter V11 14 Step 2 Remove the terminal cover Step3 Wiring HF4830S60 145 Other models...

Страница 15: ...nce and terminal position shown in the figure below Please connect the ground wire first and then the live wire and the neutral wire Ground L Live N Neutral Properly connect the AC output wire accordi...

Страница 16: ...Breaker Selection Properly connect the PV input wire according to the wire sequence and terminal position shown in the figure below PV PV input positive pole PV PV input negative pole BAT wiring metho...

Страница 17: ...h component are connected properly a circuit breaker must be installed at the battery terminal Refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection to select a right circuit breake...

Страница 18: ...urn on AC loads one by one as the AC output is normal to avoid a protection action caused by a large momentary shock due to simultaneous turning on the loads simultaneously Now the machine goes into a...

Страница 19: ...ply is preferentially used to charge the battery Only when the Mains fails the PV charging can be activated 3 Hybrid charging PV and mains hybrid charging PV MPPT charging is a priority and when PV en...

Страница 20: ...s power for charging and power supply Then the unit is equivalent to a backup UPS suitable for areas with unstable grid Switching does not affect PV charging Inverter priority mode Switch to mains sup...

Страница 21: ...peration buttons Operation buttons introduction Indicators introduction Function buttons Description SET Enter Exit Settings menu UP Previous choice DOWN Next choice ENT Confirm Enter Options under th...

Страница 22: ...that the AC output is in an overload state Indicates that the machine has been connected to the battery indicates that the remaining battery is 0 24 indicates that the remaining battery is 25 49 indi...

Страница 23: ...inverter circuit This icon is not displayed Display battery voltage battery charge total current mains charge power AC input voltage AC input frequency PV input voltage internal heat sink temperature...

Страница 24: ...INPUT V PV input voltage PV OUTPUT A PV output current 4 INPUT BATT A Input battery current OUTPUT BATT A Battery output current 5 INPUT BATT KW Battery input power OUTPUT BATT KW Battery output power...

Страница 25: ...only when the mains fails 01 SBU Inverter priority mode switching to the mains only when the battery is under voltage or lower than the set value of parameter 04 02 Output Frequency 02 50 0 Bypass se...

Страница 26: ...0 145 Max charger current AC charger PV charger Setting range 0 120A 08 Battery Type 08 USE User defined all battery parameters can be set 08 SLd Sealed lead acid battery constant voltage charge volta...

Страница 27: ...lower than the parameter 12 the inverter output will be turned off after the time set by this parameter is delayed The setting range is 5S 55S with a step of 5S It is valid for user defined battery a...

Страница 28: ...nabled if the load is null or less than 50W the inverter output is turned off after a delay for a certain period of time When the load is more than 50W the inverter automatic restart 23 Restart when o...

Страница 29: ...sabled 29 ENA Supply for industrial frequency transformer enabled 35 Battery undervoltage recovery point 35 52V default When the battery voltage is under voltage the battery voltage needs to recover m...

Страница 30: ...e voltage 55 2V 55 2V 55 2V 40 60V Adjustable Undervoltage alarm voltage 01 fault 44V 44V 44V 40 60V Adjustable Undervoltage alarm voltage recovery point 01 fault Undervoltage alarm voltage 0 8V Low v...

Страница 31: ...ge voltage 53 2V Adjustable 57 6V Adjustable 56 8V Adjustable 53 2V Adjustable 49 2 Adjustable Undervoltage alarm voltage 01 fault 43 6V Adjustable 46 8V Adjustable 49 6V Adjustable 46 4V Adjustable 4...

Страница 32: ...communication port which comes with two functions It allows direct communication with the optional host computer developed by our company through this port and enables monitoring of the equipment runn...

Страница 33: ...r APL mode the mains charging will be stopped and switched to the inverter mode 5 Battery over voltage protection When the battery voltage reaches the overvoltage disconnection point the PV and the ma...

Страница 34: ...being reversely input to Bypass 12 Bypass over current protection Built in AC input overcurrent protection circuit breaker 13 Battery input over current protection When the discharge output current of...

Страница 35: ...tage software protection 09 PvVoltHigh No PV overvoltage protection 10 PvBuckOCSw No Buck overcurrent software protection 11 PvBuckOCHw No Buck overcurrent hardware protection 12 bLineLoss No Mains po...

Страница 36: ...the device is cooled below the recovery temperature normal charge and discharge control is resumed 13 14 Bypass overload protection inverter overload protection Reduce the use of power equipment Rest...

Страница 37: ...of high temperature or burning discoloration and tighten the screws 5 Check for dirt nesting insects and corrosion and clean up as required 6 If the arrester has failed replace in time to prevent ligh...

Страница 38: ...00 4000 5000 Rated output power W 3000 4000 5000 Power factor 1 Rated output voltage Vac 230Vac Output voltage error 5 Output frequency range Hz 50Hz 0 3Hz 60Hz 0 3Hz Maximum Efficiency 92 Overload pr...

Страница 39: ...4200W PV charging current range can be set 0 60A 0 80A Charging short circuit protection Blown fuse Wiring protection Reverse polarity protection Hybrid charging Max charger current specifications AC...

Отзывы: