12 TERMINAL
GROUND
COM TERMINAL
14 TERMINAL
!
CAUTION: An interruption of 10 milliseconds or greater to the
power supplied to the solenoid of a solenoid operated valve
may cause the valve to shift. Provision must be made to prevent
power interruption of this duration to avoid unintended,
potentially hazardous, consequences.
Wiring Instructions
1. Follow all requirements for local and national electrical codes.
2. Remove end cover from base by backing off the two captive screws.
Reassemble cover to base by tightening screws from 0.8 to 1.0 N•m
(7 to 9 in-lbs).
3. An external ground connection must be
attached to the green ground screw.
4. Disregard unused
wires or terminals.
Connections
14 Solenoid
12 Solenoid
Valves with Wires
Black Wires
Red Wires
Valves with Terminal Block
14 and Com
12 and Com
(Will accept 18 to 24 Gauge Wires)
Terminals
Terminals
Valve Mounting Procedures
If valve and subbase are purchased separately, use the following
procedure to mount valve to base:
1.
Using a clean, lint free cloth, clean top surface of subbase and
bottom surface of valve body of dirt and dust.
2.
Check to insure that gasket is properly seated in gasket track on
sandwich block.
3.
Place valve assembly on top of subbase. On electrically operated
valves, line up plug with socket in base and gently press down on
valve to seat plug properly.
!
WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS
AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE
DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its
subsidiaries and authorized distributors provide product and/or system options for
further investigation by users having technical expertise. It is important that you
analyze all aspects of your application, including consequences of any failure and
review the information concerning the product or systems in the current product
catalog. Due to the variety of operating conditions and applications for these products
or systems, the user, through its own analysis and testing, is solely responsible for
making the final selection of the products and systems and assuring that all
performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features,
specifications, designs, availability and pricing, are subject to change by Parker
Hannifin Corporation and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN
EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS.
CONTACT YOUR LOCAL REPRESENTATIVE.
Installation Instructions: Form V-414CP
F3 Series Valves - Subbase Installation
2 & 3-Position, 4-Way, 5-Ports;
ISSUED: October, 1999
Supersedes: October, 1997
ECN# P27372
Introduction
Follow these instructions when installing, operating, or servicing the
product.
!
CAUTION: Solenoid versions of this valve contain solid state
components that can be damaged by transient voltage spikes,
over-voltage or high temperature. To protect against premature
solenoid failure, please read and adhere to the following:
1.
If this solenoid operated valve is used in a circuit with other inductive
loads. The solenoid should be electrically protected with a voltage
suppression device (e.g. transient voltage suppressor or varistor)
that has a minimum rating of 1.6 times the rated voltage of the
solenoid valve and sufficient capacity to dissipate the energy of other
inductive loads.
2.
Operating voltage is 85-110% of rated voltage. These limits should
not be exceeded.
Application Limits
These products are intended for use in general purpose compressed air
systems only. Compliance with the rated pressure, temperature, and
voltage is necessary - see Installation & Operating Instructions (V-410BP)
packed with valve.
Operating Pressure Range:
kPa
psig
bar
Min. (2-Position - Air Return)
140
20
1.4
Min. (2-Position w/Spring
and Air Return)
240
35
2.4
Min. (3-Position)
210
30
2.1
Max. (2 & 3-Position)
1030
150
10.3
NOTE: Solenoid operated valves, when specified with external pilot,
may have operating pressures down to vacuum in the main
valve. External pilot pressure and air pilot signals must be greater
than or equal to that in the main valve, but not outside the
ratings above.
Ambient Temperature Range: -15°C to 49°C (5°F to 120°F)
Voltage Range: Rated V10%, -15%
14 4
5
1
3
2 12
Wiring
Junction
Box
FIGURE 1: Top View (Ports located on side)
Pneumatic Division North America
Richland, Michigan 49083
Pneumatic
!
WARNING
To avoid unpredictable system behavior that can cause personal injury
and property damage:
•
Disconnect electrical supply (when necessary) before installation,
servicing, or conversion.
•
Disconnect air supply and depressurize all air lines connected to
this product before installation, servicing, or conversion.
•
Operate within the manufacturer’s specified pressure, temperature,
and other conditions listed in these instructions.
•
Medium must be moisture-free if ambient temperature is below
freezing.
•
Service according to procedures listed in these instructions.
•
Installation, service, and conversion of these products must be
performed by knowledgeable personnel who understand how
pneumatic products are to be applied.
•
After installation, servicing, or conversion, air and electrical supplies
(when necessary) should be connected and the product tested for
proper function and leakage. If audible leakage is present, or the
product does not operate properly, do not put into use.
•
Warnings and specifications on the product should not be covered
by paint, etc. If masking is not possible, contact your local
representative for replacement labels.