Introduction
Follow these instructions when installing, operating, or servicing the
product.
CAUTION: Solenoid versions of this valve contain solid state
components that can be damaged by transient voltage spikes,
over-voltage or high temperature. To protect against premature
solenoid failure, please read and adhere to the following:
1.
If this solenoid operated valve is used in a circuit with other inductive
loads. The solenoid should be electrically protected with a voltage
suppression device (e.g. transient voltage suppressor or varistor)
that has a minimum rating of 1.6 times the rated voltage of the
solenoid valve and sufficient capacity to dissipate the energy of
other inductive loads.
2.
Operating voltage is 85-110% of rated voltage. These limits should
not be exceeded.
Application Limits
These products are intended for use in general purpose compressed
air systems only. Compliance with the rated pressure, temperature,
and voltage is necessary - see Installation & Operating Instructions
(V-430DP) packed with valve.
Operating Pressure Range:
kPa
psig
bar
Min. (2-Position - Air Return)
140
20
1.4
Min. (2-Position w/Spring
and Air Return)
240
35
2.4
Min. (3-Position)
210
30
2.1
Max. (2 & 3-Position)
996
145
10.0
NOTE: Solenoid operated valves, when specified with external pilot,
may have operating pressures down to vacuum in the main
valve. External pilot pressure and air pilot signals must be
greater than or equal to that in the main valve, but not outside
the ratings above.
Ambient Temperature Range:
-15°C to 49°C (5°F to 120°F)
Voltage Range:
Rated V10%, -15%
Installation Instructions: Form V-433CP
H1 & F5 Series Valves - Manifold
Installation 2 & 3-Position, 4-Way,
5-Ports
ISSUED: November, 2000
Supersedes: October, 2000
ECN# P27873, Rev. 4
Pneumatic Division North America
Richland, Michigan 49083
Pneumatic
!
CAUTION: An interruption of 10 milliseconds or greater to the
power supplied to the solenoid of a solenoid operated valve
may cause the valve to shift. Provision must be made to
prevent power interruption of this duration to avoid
unintended, potentially hazardous, consequences.
Wiring Instructions
1.
Follow all requirements for local and national electrical codes.
2.
Remove end cover from base by backing off the four captive
screws. Reassemble cover to base by tightening screws from 0.8
to 1.0 Nm (7 to 9 in-lbs).
3.
An external ground connection must be attached to the green
ground screw of every base in an assembly.
4.
Disregard unused wires or terminals.
Connections
14 Solenoid
12 Solenoid
Valves with Wires
Black Wires
Red Wires
Valves with Terminal Block
14 and Com
12 and Com
(Will accept 18 to 24 Gauge Wires)
Terminals
Terminals
12 TERMINAL
COM TERMINAL
14 TERMINAL
GROUND
(Terminal Block
applications
only)
GROUND
(All other
applications))
14
12
!
WARNING
To avoid unpredictable system behavior that can cause personal injury
and property damage:
•
Disconnect electrical supply (when necessary) before installation,
servicing, or conversion.
•
Disconnect air supply and depressurize all air lines connected to this
product before installation, servicing, or conversion.
•
Operate within the manufacturer’s specified pressure, temperature,
and other conditions listed in these instructions.
•
Medium must be moisture-free if ambient temperature is below freezing.
•
Service according to procedures listed in these instructions.
•
Installation, service, and conversion of these products must be
performed by knowledgeable personnel who understand how pneumatic
products are to be applied.
•
After installation, servicing, or conversion, air and electrical supplies
(when necessary) should be connected and the product tested for
proper function and leakage. If audible leakage is present, or the product
does not operate properly, do not put into use.
•
Warnings and specifications on the product should not be covered by
paint, etc. If masking is not possible, contact your local representative
for replacement labels.
WARNING
Air exhausting from one valve into the exhaust gallery of the
manifold assembly may momentarily pressurize other valve
circuits open to the same gallery. Design the circuit such that
there is no hazard or consequence of damage from this action.
!
!
WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF
THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR
RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND
PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation,
its subsidiaries and authorized distributors provide product and/or
system options for further investigation by users having technical
expertise. It is important that you analyze all aspects of your application,
including consequences of any failure and review the information
concerning the product or systems in the current product catalog. Due
to the variety of operating conditions and applications for these products
or systems, the user, through its own analysis and testing, is solely
responsible for making the final selection of the products and systems
and assuring that all performance, safety and warning requirements
of the application are met.
The products described herein, including without limitation, product
features, specifications, designs, availability and pricing, are subject
to change by Parker Hannifin Corporation and its subsidiaries at any
time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR
INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE
THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.
!
FIGURE 1