WARNING
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS
AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE
DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its
subsidiaries and authorized distributors provide product and/or system options for
further investigation by users having technical expertise. It is important that you
analyze all aspects of your application, including consequences of any failure and
review the information concerning the product or system in the current product
catalog. Due to the variety of operating conditions and applications for these
products or systems, the user, through its own analysis and testing, is solely
responsible for making the final selection of the products and systems and assuring
that all performance, safety and warning requirements of the application are met.
The products described herein, including without limitation, product features,
specifications, designs, availability and pricing, are subject to change by Parker
Hannifin Corporation and its subsidiaries at any time without notice.
EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN
EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE THESE PRODUCTS.
CONTACT YOUR LOCAL REPRESENTATIVE.
Installation Instructions: Form V-432BP
F5 Series Valves - Solenoid Service
2 & 3-Position, 4-Way, 5-Ports
ISSUED: October, 1999
Supersedes: March, 1998
ECN# P27372
Introduction
Follow these instructions when installing, operating, or servicing the
product.
Application Limits
These products are intended for use in general purpose compressed air
systems only. Compliance with the rated pressure, temperature, and
voltage is necessary - see Installation & Operating Instructions (V-430CP)
packed with valve.
Operating Pressure Range:
kPa
psig
bar
Min. (2-Position - Air Return)
140
20
1.4
Min. (2-Position w/Spring
and Air Return)
240
35
2.4
Min. (3-Position)
210
30
2.1
Max. (2 & 3-Position)
996
145
10.0
NOTE: Solenoid operated valves, when specified with external pilot,
may have operating pressures down to vacuum in the main
valve. External pilot pressure and air pilot signals must be greater
than or equal to that in the main valve, but not outside the
ratings above.
Ambient Temperature Range:
-15°C to 49°C (5°F to 120°F)
Voltage Range:
Rated V10%, -15%
!
CAUTION: An interruption of 10 milliseconds or greater to the
power supplied to the solenoid of a solenoid operated valve
may cause the valve to shift. Provision must be made to prevent
power interruption of this duration to avoid unintended,
potentially hazardous, consequences.
3. An external ground connection must be
attached to the green ground screw.
4. Disregard unused
wires or terminals.
Connections
14 Solenoid
12 Solenoid
Valves with Wires
Black Wires
Red Wires
Valves with Terminal Block
14 and Com
12 and Com
(Will accept 18 to 24 Gauge Wires)
Terminals
Terminals
Servicing Solenoid Pilot
Refer to Figure 1 to aid with disassembly and reassembly. Servicing a
3-Position valve is very similar to servicing a 2-Position valve.
1. Using a clean, lint free cloth, clean the valve unit prior to servicing
solenoid.
2. Removal of valve from base is not necessary, but is recommended.
To do so, use a 4 mm hex wrench to back out the three captive
mounting screws (21) until the valve unit can be removed from the
base.
3. Loosen the two captive mounting screws (11) and then remove the
solenoid coil (9) and sandwich adapter (13) as a unit from the operator
adapter (15).
4. Back out screw (4) until the solenoid coil can be removed from the
sandwich adapter. This screw is located between the flat electrical
pins (5) of the solenoid coil; this screw will remain captive.
NOTE: Using a clean, lint free cloth, clean all sealing surfaces for gaskets
prior to their installation.
NOTE: Except for the gasket that is located between the solenoid coil
and sandwich adapter, apply a light coating of grease (supplied
with kits) to all gaskets.
5. Replace the gasket (10) which is located between the solenoid coil
and the sandwich adapter (using a new gasket from a service kit).
6. Slide the new replacement solenoid coil into the sandwich adapter,
such that the 3 pins line up with the three slots in the sandwich
adapter.
Pneumatic Division North America
Richland, Michigan 49083
Pneumatic
!
WARNING
To avoid unpredictable system behavior that can cause personal injury
and property damage:
•
Disconnect electrical supply (when necessary) before installation,
servicing, or conversion.
•
Disconnect air supply and depressurize all air lines connected to
this product before installation, servicing, or conversion.
•
Operate within the manufacturer’s specified pressure, temperature,
and other conditions listed in these instructions.
•
Medium must be moisture-free if ambient temperature is below
freezing.
•
Service according to procedures listed in these instructions.
•
Installation, service, and conversion of these products must be
performed by knowledgeable personnel who understand how
pneumatic products are to be applied.
•
After installation, servicing, or conversion, air and electrical supplies
(when necessary) should be connected and the product tested for
proper function and leakage. If audible leakage is present, or the
product does not operate properly, do not put into use.
•
Warnings and specifications on the product should not be covered
by paint, etc. If masking is not possible, contact your local
representative for replacement labels.
Wiring Instructions
1. Follow all requirements for local and national electrical codes.
2. Remove end cover from base by backing off the two captive screws.
Reassemble cover to base by tightening
screws from 0.8 to 1.0 N•m (7 to 9 in-lbs).
GROUND
12 TERMINAL
COM TERMINAL
14 TERMINAL