background image

15

3.4.3  Heater Wiring

In cold or damp environments, the heater serves to prevent the 
electric solenoid valves from freezing due to cold temperatures 
or condensation. If optional solenoid valve heater is purchased, 
each 4 solenoid valve enclosures will contain a 70-watt car-
tridge heater, 6, 8 and 10 solenoid valve enclosures will contain 
a 120-watt cartridge heater internally prewired to a thermostat.

The customer must provide a 100-130VAC, 50/60Hz, 1 amp 
power to the heater circuit for each module. The power must be 
available to the module solenoid valve enclosure(s) at all times 
(even when the blower is shut down) to ensure temperature 
regulation inside each solenoid valve enclosure is continual. 
When multiple module solenoid valve enclosures with heaters 
are installed, daisy chain the wiring so that each heater will have 
100/115VAC, 50/60 Hz at all times. Make certain enough cur-
rent is available to supply all heaters.

Example: If three solenoid valve enclosures are supplied with car-

tridge heaters, make certain the voltage supply can deliver 3 
amps (1amp per heater). 

3.5  Compressed Air Connection

  Do not allow water and/or oil from the compressed 

air system into the compressed air manifold reservoir. 
To ensure a clean, dry air supply, especially when the 
unit is installed outdoors, a water filter with automatic 
drain and a coalescing filter should be installed (refer 
to Figure 10).

Clean, dry, 90-110 PSIG (6.2-7.6 BAR) compressed air is required 
for the pulse cleaning system to function properly. Compressed 
air consumption is noted on the Parker sales drawing. A shut-off 
valve, pressure regulator and pressure gauge should be installed 
close to the SFC unit. Parker recommends dedicated oil and water 
removal filters be used to ensure clean, dry air is delivered to the 
pulse system. Contact your local SFC representative for informa-
tion about Parker’s Pneumatic Valve Assembly. Refer to Figure 10 
for recommended compressed air piping and Table 1 below for 
proper compressed air line sizing.

NOTE:   Using Table 1, select the proper diameter compressed air 

line pipe to supply your dust collector. The final connection 
size is a female 1” NPT fitting on each module.

NOTE:   Purge the compressed air line to remove any debris prior 

to making the final connection to the SFC compressed air 
manifold(s). Apply pipe fitting sealant on all compressed air 
supply pipe fittings and connections.

3.6  Assembly of Optional Equipment

3.6.1 Blower Purge Package Installation

TIP OVER HAZARD

 Anchor dust collector to concrete pad prior to install-
ing blower assembly. Make certain all hardware is 
properly tightened.

If a top-mount blower package was ordered, read the manu-

facturer’s Installation and Operation Manual completely before 

installing the blower. The blower Installation and Operation 

Manual is attached to the fan package. Perform all pre-installa-

tion checks prior to installing the blower.

TIP OVER HAZARD

If blower package has a 20 HP (15 kW) motor or larger, 
ensure the blower support legs are installed beneath 
the clean air plenum of the module to which the blower 
will be mounted.

For top-mount blower packages of 20 HP (15 kW) or larger, an 
additional set of support legs is provided. The additional support 
legs must be mounted under the filter module supporting the blower 
package (refer to Figure 11). Bolt the mounting plate to the bottom 
of the appropriate clean air plenum with the hardware provided. 
Bolt the leg assemblies to the mounting plate with the hardware 
provided. Secure leg assemblies to the concrete mounting pad with 
appropriate anchoring hardware.

Remove the clean air plenum cover plate on top of the filter module 
and save the mounting hardware. Ensure ribbon gasket remains on 
the unit. Lift blower package using safe, suitable means and position 
blower base holes over filter module holes with blower discharge 
pointing in the desired direction. Secure with bolt/washer assem-
blies previously removed. Top-mount blower packages include a 
blower outlet damper. Install blower damper to outlet of blower 
assembly with hardware provided.

If the blower package is a ground-mount blower, read the manu-
facturer’s Installation and Operation Manual completely before 
installing the blower. The blower Installation and Operation Manual 
is attached to the fan package. Perform all pre-installation checks 
prior to installing the blower.

Outlet ducting from the SFC unit to the blower package can be con-
nected to either the top or bottom clean air section access panel(s). 
It is recommended industry practice to provide vibration isolation 
between the blower inlet and the dust collector outlet ducting.

 

!

  D A N G E R

 

!

  D A N G E R

Pipe Diameter

1 inch (25mm)

1-1/2 inch (38mm)

2 inch (51mm)

Number 

of Filter 
Section 

Modules

1-3
3-5

+5

or

Distance of Supply Air 
Piping Run From Main 

Compressor Line

50 feet (15 meters)

100 feet (31 meters)

+100 feet (+31 meters)

Table 1

    

CAUTION

Содержание SFC

Страница 1: ...Downward Flow Cartridge Dust Collector Owner s Manual Model SFC...

Страница 2: ...Parker Parker Order _________________________________________________________________ Unit Model ___________________________________________________________________ Unit Serial ______________________...

Страница 3: ...odule Sections applies to 4 or more modules 6 3 4 Electrical Installation 11 3 4 1 Mounting the Controls 11 3 4 2 Solenoid Valve Enclosure Wiring 11 3 4 3 Heater Wiring 15 3 5 Compressed Air Connectio...

Страница 4: ...Dust Removal 24 5 3 Servicing the Compressed Air Components 24 5 4 Servicing the Direct Drive Blower and Motor System 24 5 5 Servicing Cartridge Media 25 5 6 Servicing Optional Return Air Safety Filt...

Страница 5: ...t collector The unit should be inspected frequently and dirt removed to prevent excessive accumulation which may result in flash over or fire damage The SFC system should not be used to support person...

Страница 6: ...nt should be by a licensed contractor that is also experienced in potential fire and explosion hazards and adheres to related local state and federal codes standards laws and regulations Parker is not...

Страница 7: ...v Page intentionally left blank...

Страница 8: ...ding in non traffic areas even though the dust collector is equipped with an explosion vent 2 Introduction Thank you for selecting Parker dust collection equipment to assist you in your commitment to...

Страница 9: ...nism provides brief bursts of compressed air directed through the diaphragm valves toward the cartridge filter This pulsing action dislodges the collected particles from the media where they fall into...

Страница 10: ...crating strapping and hold down bolts Locate all hardware bags sealant and other assembly materials provided with your unit 3 Installation 3 1 Off Loading and Inspection SFC dust collector modules are...

Страница 11: ...4 FIGURE 2 SFC Typical SINGLE UNIT Installation Diagram PARKER PARKER 44 10335 0001...

Страница 12: ...5 FIGURE 3 Recommended Unit Clearances 44 10337 0001...

Страница 13: ...hopper and filter module together Securely tighten all hardware at the filter module and hopper Recheck leg assembly sway braces to ensure they are tight Install fasteners bolt flat washer lock washer...

Страница 14: ...7 FIGURE 4 Single Hopper SFC 44 10309 0001...

Страница 15: ...8 FIGURE 5 Multiple Hopper SFC 44 10309 0002...

Страница 16: ...9 FIGURE 6 Multiple Hopper SFC 44 10309 0003...

Страница 17: ...10 FIGURE 7 Multiple Modules SFC 44 10310 0001...

Страница 18: ...pulse cleaning Motor starter with Digital Pulse Control DPC for on demand pulse cleaning VFD with DPM for continuous pulse cleaning VFD with DPC for on demand pulse cleaning Refer to Parker sales orde...

Страница 19: ...12 FIGURE 8 SFC Pressure Gauge Installation 44 10333 0001 Rev A...

Страница 20: ...13 FIGURE 9 Solenoid Wiring to Pulse Controls for 2 3 4 and 5 Tier Units...

Страница 21: ...14 FIGURE 10 Pneumatic Valve Assembly 44 10332 0001...

Страница 22: ...l compressed air supply pipe fittings and connections 3 6 Assembly of Optional Equipment 3 6 1 Blower Purge Package Installation TIP OVER HAZARD Anchor dust collector to concrete pad prior to install...

Страница 23: ...16 FIGURE 11 Legs Support Top Mount Blower 44 10331 0001 NOTE FOR BLOWERS 20 HP OR LARGER SUPPORT LEGS ARE REQUIRED TO BE INSTALLED UNDER THE CLEAN AIR PLENUM...

Страница 24: ...17 FIGURE 12 Abrasive Inlet Installation 44 10338 0001...

Страница 25: ...ry air lock Do not allow any object to be placed in or near the rotary air lock during operation Verify rotary air lock rotation matches rotation arrows affixed to assembly 3 6 4 Abrasive Inlet Instal...

Страница 26: ...s not designed for dust storage The slide gate should remain open during normal operation 3 6 6 Inlet Cover and Blank Cover Plate Installation Inlet collar and blank cover plates bolt directly to the...

Страница 27: ...20 FIGURE 16 EDAP Interconnection FIGURE 15 EDAP Installation 48 10007...

Страница 28: ...transport an assembled 5 high unit due to height restrictions within the vehicle When shipping this unit it will be necessary to ship the EDAP separately This will require the customer to assemble th...

Страница 29: ...interchange at motor junction box Engage starter disconnect switch start blower and recheck rotation NOTE Proper blower rotation is required to move the designed amount of air A blower rotating in the...

Страница 30: ...23 FIGURE 17 SFC Series Door Filter Installation 44 10329 0001...

Страница 31: ...timerboard to the Continuous Clean position Or if the system is sup plied with DPC Pulse Control place the Continuous Clean PS switch on the timerboard to PS position The MOT AUX terminals at the time...

Страница 32: ...ace prior to being closed A flat solid section of door handle will be visible when door assembly is in the properly closed position Refer to Figure 17 If cam surface of the door handle is visible Quic...

Страница 33: ...for HEPA filters TABLE 2 Cartridge Filters CARTRIDGE FILTER PARKER PART NUMBER GENERAL DESCRIPTION OF FILTER MEDIA ProTura Nanofiber 33 10089 ProTura Nanofiber layer on cellulose ProTura Nanofiber FR...

Страница 34: ...l This may require bending panel sections away from the frame for frame removal Care should be taken to avoid sharp panel edges during this activity 4 Dispose of the removed rupture panel in accordanc...

Страница 35: ...proper motor starter overload rating against full load amps on motor name plate Adjust or replace overloads as required Ensure drum is properly sealed against drum lid package Ensure drum lid package...

Страница 36: ...ge to the timer board and voltage output from timer boards to solenoid valves Consult DPM DPC Pulse Control Panel Installation and Operation Manual for additional assistance Reduce high set point on D...

Страница 37: ...30 7 Illustrated Parts FIGURE 21 SFC Series 44 10330 0001 FIGURE 22 SFC Series Explosion Vents...

Страница 38: ...0020 20 Gallon Drum Lid 9 45 10022 0055 55 Gallon Quick Release Collar 9A 45 10022 0020 20 Gallon Drum Quick Release Collar 10 15 0233 14 Hose Clamp 11 15 0202 14 Flexible Duct 12 18 0944 14 Adapter...

Страница 39: ...32 Page intentionally left blank...

Страница 40: ...or misuse misapplication or normal wear and tear e Equipment not properly installed operated and maintained under normal conditions and recommended applications As Buyers exclusive remedy for any def...

Страница 41: ...shooting effort details 5 Description of physical location and or environment details The Buyer shall cooperate with PARKER in its investigation and provide full information and documentation concerni...

Страница 42: ...arker com dhfns Hiross Zander Essen Germany 49 2054 9340 www parker com hzfd Padova Italy 39 049 9712 111 www parker com hzfd Engine Filtration Water Purification Racor Dewsbury England 44 0 1924 487...

Отзывы: