English
6 / 8
ICEP002-005
4.6 Setting clock/date.
(see fi g. 1/3)
1. Press the buttons “
” “
”, together to enter in the menu
“
FrEE
”.
2. Press the button “
set
” to enter in the menu “
Ai
”.
3. Press the button “
” to enter in the il menu “
CL
”.
4. Press the button “
set
” to enter and visualize the parameter
“
HOUr
”.
5. Press the button “
set
” until the fl ashes of the parameter “
HOUr
”.
6. Select the fl ashing parameter “
HOUr
”/“
dAtE
”/“
4EAr
” using the
button “
” and press “
set
” to enter.
7. Change the fl ashing value using the buttons “
”and “
” (up
and down) and press the button “
set
” to confi rm.
8. Press the button “
esc
” to return to the menu “
FrEE
”.
9. Press the buttons “
” “
” together to exit.
Fig.3
Y
set
dr4
Y
Y
FrEE
Y
Ai
Y
CL
set
Y
HOUr
4EAr
Y
Y
set
Y
set
Y
01.09
set
Y
2015
17.15
set
Y
Y
FrEE
HOUr
dAtE
set
Y
3 sec.
18.20
esc
Y
!
The memory of the “clock / date” has a maximum duration of
three days, so if the controller is left without power for more than
three days, the data set hour / month / year are lost.
Adjust the clock at the start up of the machine, and whenever
necessary.
4.7 Visualization of temperature probes B1,B2
(see fi g.1/4)
Fig.4
set
12.5
Y
b1
Y
b2
3
sec.
5.0
Y
1. Turn the main swicth (QS) to “ON” and wait for the “
OFF
” visualiza-
tion.
2. Press the button “
set
” to start up.
3. The display shows the temperature of the probe B1.
4. Using “
”and “
” buttons select the probe (B2), wait for 3
seconds to see the temperature value.
5. Press the button “
esc
” to exit
4.8 Alarms management
(see fi g.1/5)
Fig.5
set
set
!
23.5
Y
Y
Pb
Y
Y
AL
set
Er__
Er__
Y
ALARM
Y
1. Press the button “
set
” to start up.
2.
!
Alarm ON (led on: red).
3. Press the button “
set
” to enter in the menu, using “
”and “
”
buttons select the parameter “
AL
” .
4. Press the button “
set
” to see the alarm code.
5. Press the button “
” to see the next code.
6. Press the button “
esc
” to exit.
4.8.1
Analog /Digital input alarms
CODICE
DESCRIZIONE
AZIONE
RESET
Er01
Sensor B1 cutout or broken
Alarm
A
Er02
Sensor B2 cutout or broken
Alarm
A
Er03
Sensor B3 cutout or broken
Alarm
A
Er04
High pressure
Alarm
M
Er05
Low pressure
Alarm
M
Er06
Pump thermal cutout
Alarm
M
Er07
Low water level
Alarm
M
Er08
High pressure trasducer cutout or
broken
Alarm
A
Er10
Sensor B4 cutout or broken
Warning
M
Er12
Compressor thermal *
Alarm
M
Er14
High temperature sensor B1
Alarm
A
Er15
Low temperature sensor B1
Alarm
A
Er16
High temperature sensor B2
Alarm
A
Er17
Low temperature sensor B2
Alarm
A
Er18
High temperature sensor B3
Alarm
A
Er19
Low temperature sensor B3
Alarm
A
Er20
Antifreeze
Alarm
A
Er21
Exceeded compressor working hours
Warning
A
Er23
Phase monitor
Alarm
M
Er24
Exceeded unit working hours
Warning
A
Er25
Communication expansion
Alarm
A
Er26
Controller memory
Warning
A
*
!
(Only oil model)
If the evaporator temperature falls below 5°C for more than 120s
then an alarm “
Er12
“ will occur, blocking the unit.
!
Press the button
“
esc
”
to reset alarms (5sec).