5 Maintenance

a) The machine is designed and built to guarantee continuous opera-

tion; however, the life of its components depends on the mainte-
nance performed.

b) Z When requesting assistance or spare parts, identify the machine 

(model and serial number) by reading the data plate located on the 
unit. 

c) Circuits containing 5t < xx < 50t of CO2  are checked to identify 

leaks at least once a year.
Circuits containing 50t < xx < 500t di CO2 are checked to identify 
leaks at least once every six months. ((EU) No. 517/2014 art. 4.3.a, 
4.3.b).

d) For machines containing 5t CO2 ore more, the operator must keep a 

record stating the quantity and type of refrigerant used, an quantities 
added and that recovered during maintenance operations, repairs 
and fi nal disposal ((EU) No. 517/2014 art. 6). .An example of this 
record sheet can be downloaded from the site: www.polewr.com.

5.1 General instructions

Before performing any maintenance, make sure the power to the 

refrigerator is disconnected.

Y

 Always use the Manufacturer’s original spare parts: otherwise the 

Manufacturer is relieved of all liability regarding machine malfunction-
ing.

Y

 In case of refrigerant leakage, contact qualifi ed and authorized 

personnel.

Y

 The Schrader valve must only be used in case of machine mal-

function: otherwise any damage caused by incorrect refrigerant charg-
ing will not be covered by the warranty.

5.2 Preventive maintenance

To guarantee lasting maximum chiller effi ciency and reliability, carry out:

every 6 months -

 clean the condenser fi ns and make sure com-

pressor electrical absorption is within the dataplate values;

Maintenance 

 (par.7.7) 

   

a)  kit for maintenance;

   

b)  service kit;

 

c)  individual spare parts.

5.3 Refrigerant

Charging: any damage caused by incorrect charging carried out 

by unauthorized personnel will not be covered by the warranty.

Y

 The equipment contains fl uorinated greenhouse gases.

At normal temperature and pressure, the R407C refrigerant is a colour-
less gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid ac-
cording to Directive PED 2014/68/EU);
GWP (Global Warming Potential) = 1774.

In case of refrigerant leakage, air the room.

5.4 Dismantling

The refrigerant and the lubricating oil contained in the circuit must be 
recovered in conformity with current local environmental regulations.
The refrigerant fl uid is recovered before fi nal scrapping of the equip-
ment ((EU) No. 517/2014 art.8).

%

Recycling

Disposal

frame and panels

steel/epoxy resin polyester

tank

aluminium/copper/steel

pipes/collectors

copper/aluminium/carbon steel

pipe insulation

NBR rubber

compressor

steel/copper/aluminium/oil

condensator

steel/copper/aluminium

pump

steel/cast iron/brass

fan

aluminium

refrigerant

R407C (HFC)

valve

brass/copper

electrical cable

copper/PVC

Содержание Hyperchill ICE183

Страница 1: ...Hyperchill 50Hz ICE150 ICE183 ICE230 DATE 29 04 2019 Rev 28 CODE 398H271650 IT Manuale d uso EN User Manual ES Manual de uso DE Benutzer Handbuch...

Страница 2: ......

Страница 3: ...il diritto di modificare le infor mazioni contenute nel presente manuale senza alcun preavviso Ai fini di una completa ed aggiornata informazione si raccomanda all utente di consultare il manuale a b...

Страница 4: ...iempire il circuito assicurarsi che le tubazioni siano pulite In caso contrario effettuare un lavaggio accurato Y Se il circuito idraulico di tipo chiuso in pressione consigliabile installare una valv...

Страница 5: ...d installazione della macchina La corrente nominale In di tale magnetotermico deve essere uguale a FLA e la curva di intervento di tipo D 5 Valore massimo dell impedenza di rete 0 274 ohm Controlli s...

Страница 6: ...con pompa OFF Pmin P1 P0 Pmax Esempio n 1 Condizioni circuito chiuso a pressione P0 di 2 bar dati targa pompa Pmin 1bar Pmax 3bar regolare l uscita valvola per una pressione di 3bar P1 5Bar Esempio n...

Страница 7: ...Differenziale termostatazione B1 dIA U 1 0 Modalit funzionamento resisten za antigelo paragrafo 4 4 8 1 FUA U 0 Modalit attivazione resistenza antigelo paragrafo 4 4 8 2 AbrA U 2 Set point attivazione...

Страница 8: ...one circuito 2 M 4 6 2 Allarmi da ingressi analogici AI CODICE DESCRIZIONE RESET B1 HAI Allarme alta temperatura uscita acqua serbatoio Avviso LAI Allarme bassa temperatura uscita acqua serbatoio A St...

Страница 9: ...la macchina in caso contrario i danni provocati da errata carica di refrigerante non verranno riconosciuti in garanzia 5 2 Manutenzione preventiva Per garantire nel tempo la massima efficienza ed affi...

Страница 10: ...ASATO SOSTITUIRE IL FILTRO ALETTE DEL CONDENSATORE SPORCHE PULIRE LE ALETTE DEL CONDENSATORE SUPERFICIE DEL CONDENSATORE OSTRU ITA LIBERARE LA SUPERFICIE FRONTALE DEL CONDENSATORE PORTATA ACQUA INSUFF...

Страница 11: ...ves the right to modify this manual at any time For the most comprehensive and updated information the user is advised to consult the manual supplied with the unit 1 4 Residual risks The installation...

Страница 12: ...the water inlet and outlet pipelines Y If the hydraulic circuit is intercepted by automatic valves protect the pump with an anti hammering system Y If the hydraulic circuit is emptied for shut down p...

Страница 13: ...ck that the machine and the auxiliary equipment are earthed and protected against short circuit and or overload Once the unit has been connected and the upstream main switch closed thereby connecting...

Страница 14: ...limit values Pmax and Pmin indicated on the pump data plate P1 pressure with pump ON P0 pressure with pump OFF Pmin P1 P0 Pmax Example n 1 Conditions closed circuit pressure P0 2 bar pump data plate...

Страница 15: ...hour counter threshold tH4 U 0 4 4 9 Pump parameters PARAMETER CODE TYPE DEFAULT Pump stop delay dP5 U 5 Pump start delay dPA U 5 4 4 10 Antifreeze heater parameters PARAMETER CODE TYPE DEFAULT Set po...

Страница 16: ...analogici AI CODE DESCRIPTION RESET B1 HAI Tank water outlet water high tempera ture alarm Warning LAI Tank water outlet water low tempera ture alarm A StI Sensor open circuit or short circuit M B2 H...

Страница 17: ...unction otherwise any damage caused by incorrect refrigerant charg ing will not be covered by the warranty 5 2 Preventive maintenance To guarantee lasting maximum chiller efficiency and reliability ca...

Страница 18: ...FILTER CLOGGED RENEW THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CON DENSER INSUFFICIENT WATER FLOW INCREASE THE FLOW RATE...

Страница 19: ...abricante se reserva el derecho de modificar sin previo aviso la informaci n de este manual Para que la infor maci n resulte completa se recomienda al usuario consultar el manual a pie de m quina 1 4...

Страница 20: ...talar filtros de red en los tubos de entrada y salida del agua Y Si el circuito hidr ulico posee v lvulas autom ticas de corte proteger la bomba con sistemas contra golpe de ariete Y Si se vac a el ci...

Страница 21: ...ocircuitos y sobrecargas Una vez conectado el equipo cuando se cierra el interruptor ge neral de alimentaci n para energizarlo la tensi n en el circuito el ctrico alcanza valores peligrosos Se recomie...

Страница 22: ...P0 y los valores l mite de presi n Pm x y Pm n indicados en la placa de datos de la bomba P1 presi n con bomba ON P0 presi n con bomba OFF Pm n P1 P0 Pm x Ejemplo n 1 Condiciones circuito cerrado a p...

Страница 23: ...compresor 4 tH4 U 0 4 4 9 Par metros de la bomba PAR METRO C DIGO TIPO PREDET Retardo apagado de la bomba dP5 U 5 Retardo encendido bomba dPA U 5 4 4 10 Par metros de la resistencia antihielo PAR MET...

Страница 24: ...le circuito 2 M 4 6 2 Alarmas desde las entradas anal gicas AI C DIGO Descripci n Restabl B1 HAI Alarma alta temperatura salida de agua dep sito Avviso LAI Alarma baja temperatura salida de agua dep s...

Страница 25: ...el equipo de lo contrario los da os causados por una carga incorrecta de refrigerante no ser n reconocidos en garant a 5 2 Mantenimiento preventivo Para garantizar la m xima eficacia y fiabilidad del...

Страница 26: ...TASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSADOR OBSTRUIDA LIBERAR LA SUPERFICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INSUFICIE...

Страница 27: ...en f r die korrekte bzw in vern nftiger Weise vorhersehbare Nutzung der Anlage bzw der Bauteile ausreichen ACHTUNG Der Hersteller beh lt sich das Recht vor die in dem vorliegenden Handbuch enthaltenen...

Страница 28: ...geschlossenem Wasserkreislauf ist die Installation eines 6 Bar geeichten Sicherheitsventiles erforderlich Y Am Wasser Ein und Austritt sollten stets geeignete Siebfilter installiert werden Y Wird der...

Страница 29: ...Nennstrom In des Schutzschalters muss FLA entsprechen und die Ausl sekennlinie muss vom Typ D sein 5 Maximaler Netzimpedanzwert 0 274 Ohm Nachfolgende Kontrollen Sicherstellen dass die Einheit und daz...

Страница 30: ...en P1 Druck Pumpe ON P0 Druck Pumpe OFF Pmin P1 P0 Pmax Beispiel Nr 1 Bedingungen Geschlossener Kreislauf bei P0 Druck von 2 bar Daten des Pumpenschilds Pmin 1bar Pmax 3bar Den Ventilausgang f r einen...

Страница 31: ...AMETER CODE TYP DEFAULT Verz gerung Pumpenstopp dP5 U 5 Verz gerung Pumpenstart dPA U 5 4 4 10 Parameter des Frostschutzwiderstands PARAMETER CODE TYP DEFAULT Sollwert Einstellung B1 SEA U 7 0 Differe...

Страница 32: ...en AI CODE Beschreibung R ckstellung B1 HAI Alarm hohe Temperatur am Wassertan kauslauf Warnmeldung LAI Alarm niedrige Temperatur amWasser tankauslauf A StI Sensor ge ffnet oder Kurzschluss im Sensor...

Страница 33: ...usetzen anderenfalls werden Sch den infolge unkorrekter K ltemittelbef llung nicht von der Garantie abge deckt 5 2 Vorbeugende Wartung F r eine stets optimale Effizienz und Zuverl ssigkeit des Chiller...

Страница 34: ...ER ERSETZEN RIPPEN DES KONDENSATORS VERSCHMUTZT RIPPEN DES KONDENSATORS REINIGEN OBERFL CHE DES KONDENSATORS BEDECKT BEDECKUNG AN FRONTOBERFL CHE DES KONDENSATORS ENTFERNEN WASSER VOLU MENSTROM UNZU R...

Страница 35: ......

Страница 36: ...co MI Italy Sede Operativa Gas Separation and Filtration Division EMEA Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e m...

Отзывы: