2. BitStorm 1900 Installation and Testing
1900-A2-GN20-00
BitStorm 1900 Installation and Maintenance Guide
2-41
Step
Procedure
(continued)
4.)
Install the air filter frame.
a.) The filter must be removed.
b.) Slide the frame into place.
5.)
Install the air filter for the DC fan tray. (DO NOT install a filter in the
AC fan tray).
NOTE: An air filter must be installed and maintained in the DC Fan Tray for
NEBs compliance.
a.) Verify filter is installed in the frame.
b.) Slide the unit into the fan tray.
NOTE: Installed air filters must be changed every 6 months. Bulk packs of
5 NEBs Air Filters (Part # 0100085-01) are available.
STOP
<RXKDYHFRPSOHWHGWKLVWDVN
!
WARNING: POSSIBLE EQUIPMENT DAMAGE! AC Fan
Trays are shipped with an air filter frame. To
ensure proper airflow, the frame must be
installed. DO NOT install an air filter for the
AC Fan Tray, only the frame.