TAMPER/WIRE FAULT DEFINITIONS AND OPTIONS
When using 2 zone resistors, the panel offers four possible definitions for tamper/wiring recognition,
independent of zone definition.
"Tamper/wire” disabled
(Address 088, Key [10] "off", Key [11] "off")
Tamper/wiring failure recognition is disabled. (Not allowed by UL listed systems, must be enabled.)
"Trouble" enabled
(Address 088, Key [10] "off", Key [11] "on")
Tamper/wiring failure will generate an alarm, when armed. A trouble report code will be sent to the central
when disarmed.
"Silent alarm" enabled
(Address 088, Key [10] "on", Key [11] "off")
Tamper/wiring failure will generate a silent alarm (no siren) when the system is disarmed. Alarm and
trouble report codes will be sent to the central when the system is armed.
"Audible alarm" enabled
(Address 088, Key [10] "on", Key [11] "on")
Tamper/wiring failure will generate an audible alarm armed or disarmed (siren). Alarm and trouble
report codes will be sent to the central.
Exception: When the zone definition is "24 hour", the tamper definition follows the audible/silent
alarm arm definition of the "24 hour" zone.
Tamper recognition addresses:
Tamper report and restoration codes should be programmed at addresses 472-478 and 510.
FIRE CIRCUIT
The fire zone (enabled by defining zone 3 as "24 hour”) should always be connected with a
1K
W
W
EOL resistor (PN201100200-PRT on UL systems). If there is a line short in the fire zone,
a fire alarm will be generated. If the line is "open", a "fire loop" trouble report will be sent to the
central and trouble indicator [11] will illuminate on the LED keypad.
For UL/ULC installations, a 4 wire, latching, smoke detector (UL - Falcon Model 5454, ULC -
BRK Model 2412) must be used. To supervise power supply, an “end of line” relay (Model
MR3) is installed. This relay’s contacts will cause a FIRE TROUBLE in the event the power
is interrupted.
To reset (unlatch) smoke detectors after an alarm, power to detectors must
momentarily be interrupted. To do so, connect the negative (-) side of smoke
detector power to PGM1. PGM1 should then be programmed “Timed N.C.” (nor-
mally closed), programmed to “open” when any two keys on the keypad are
pressed simultaneously.
Example:
To program
PGM
1
to conduct smoke detector reset when [
CLEAR
] and [
ENTER
]
are pressed at the same time.
Address 039 = [
BYP
] [2
ND
]
Address 040 = [5] [10]
Address 042 = [2
ND
] [6]
Address 056 = [10] [10] [4]
TELEPHONE LINE CONNECTION
Connect the incoming telephone company wires into "
TIP
" and
"
RING
". Wires should then be run from "
T
1" and "
R
1" to the installa-
tion's phone system.