![Panduit UPS003024024015 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/panduit/ups003024024015/ups003024024015_operation-manual_3605770004.webp)
©
Panduit Corp. 201
4
OPERATION MANUAL
UPS003024024015
Page: 3 of 29
ACCESSORIES
Load Sense Module Panduit part number UPS003LSM
UPS GENERAL SPECIFICATIONS
Model Number
UPS003024024015
Input Power
Voltage: 24.0 to 28.0 VDC
Power Minimum: 20 W
with no load, charging on slow charge
setting per section 4.7.2
Power Maximum: 88
W with 35 W load, charging on fast charge setting per 4.7.2
Protection: Over-voltage shut down at 32VDC. Maximum overvoltage is +60VDC at 25°C ambient. Reverse
voltage maximum is -60VDC at 25°C ambient.
Output Power
Voltage: Input present: 500 mV drop at 35 W load
Input not present: 21.0 to 23.0 VDC
Current: 1.6 A maximum
Short circuit rating: 3.6 to 4.6 A
Environmental
Operating Temperature: -40 to +60°C.
Storage (non-operational) Temperature: -40 to +70°C.
Humidity: 0 to 95% RH, noncondensing
Operational Vibration: 2G at 10 to 500 Hz
Operational Shock: 20G (11ms 3 bumps / direction, 18 bumps in total)
Compliance
o
FCC Title 47 CFR 15 Subpart B Emissions Class A
o
CAN ICES-3(A)/NMB-3(A), ICES-003 Issue 5
o
UL 1778 and
CSA C22.2 No. 107.3-05
“Uninterruptible Power Supply Equipment”
o
UL 508 and CSA-C22.2 No. 14 “Industrial Control Equipment”
o
UL 60950-1, 2
nd
ed, 2011-12-19, CSA C22.2 No. 60950-1-07, 2
nd
ed, 2011-12
"Information Technology Equipment - Safety - Part 1: General Requirements"
o
(Low-Voltage Directive*) IEC 60950-1:2005+AM 2009, EN 60950-1:2006+A1:2010+A11:2009+A12:2011
"Information Technology Equipment - Safety - Part 1: General Requirements"
o
ISA 12.12.01:2013, CSA C22.2 No. 213-1987M (R2013) “Standard For Nonincendive Electrical Equipment
for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations”
o
RoHS All materials and components used must meet the material restrictions of European Directive
2002/95/EC on the Restriction of Hazardous Substances
o
IP20 per IEC 60529
o
IEC Ex (
pending
)