SMARTZONE UPS USER MANUAL
90
Fault
Code Fault Description
Fault
Type
Buzzer
LED
Action to Take
00A
Output Discharge SCR
Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
00C
Battery Charge SCR
Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
00E Fan Fault
Critical Continuous
Red
Alert On
Remove ventilation obstructions
and Reboot the UPS unit
011 Fan Power Supply Error Critical Continuous
Red
Alert On
Remove ventilation obstructions
and Reboot the UPS unit
012 UPS Over Temperature Critical Continuous
Red
Alert On
Ensure that Ambient operating
temperature is at or below 40C
Reduce the load
Check if the battery group is set
correctly
Remove ventilation obstructions.
Reboot the UPS unit
013 DC Bus Soft Start Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
014 Battery Charger Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
016 Rectifier
Communications Error Critical Continuous
Red
Alert On
Reboot the UPS unit
019 Rectifier Initialization
Fault
Critical Continuous
Red
Alert On
Reboot the UPS unit
01D Power Block not
Connected
Critical Continuous
Red
Alert On
Reboot the UPS unit
01E Rectifier Error
Critical Continuous
Red
Alert On
Reboot the UPS unit
024 Battery Charger
Overcurrent
Critical Continuous
Red
Alert On
Ensure the battery group is set
correctly
Remove ventilation obstructions
Reboot the UPS unit
041 Inverter Error
Critical Continuous
Red
Alert On
Ensure that the proper copper bus
bars are installer for the desired
configuration
Reboot the UPS unit