Figure 44: Parallel Mode System Setup Page (3-Phase UPS)
Refer to the Parallel Mode subsection in Section 1 above for the proper steps to
connect and configure a parallel mode system.
Press the left or right arrow on the Parallel ID line to select a number from 1 to 4 for the
parallel ID number of that UPS. The default is 1.
Press the left or right arrow on the Parallel Basic Units line to select the number of units
(2 to 4) in the Parallel System Configuration. The default number is 2.
Press the left or right arrow on the Parallel Redundancy Units line to select the number
of units (0 to 3) in the Parallel System that are redundant units. The default number is 0
(meaning no redundancy).
Note:
Redundant units are not calculated in the overall capacity of the parallel system.
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the up and over arrow to return to the Advanced Setting Menu page.
Output Setup Page
This page allows the user to set the UPS output parameters.