SMARTZONE UPS USER MANUAL
67
changed, the warning will alert at 1095 – 372 = 723 days after the installation date. This
warning is intended to allow the user to order replacement battery cartridges and
replace the cartridges before the replacement alarm is triggered. The user should
change this interval based on their company policies for replacing VLRA batteries.
On the Battery Replacement Alarm line, press the number in front of the Day to type in
the number of days less than 1095 days from the install date that the UPS will notify the
user (via an alarm) that the battery cartridges should be replaced. The default is 365
days (7 days after the Battery Replacement Notification warning). This value has a
range from 0 to 365 days. If the default value is not changed, the alarm will alert at 1095
– 365 = 730 days (or 2 years) after the installation date. This alarm is intended to notify
the user that the battery cartridges should be replaced now. The user should change
this interval based on their company policies for replacing VLRA batteries.
After making all the necessary changes on each page, press the “Save Config” button
before leaving the individual page to save the changes.
Press the up arrow to go to the previous page. Press the up and over arrow to return to
the Advanced Setting Menu page.
Bypass Setup Page
This page allows the user to set the bypass limits and ranges on the UPS. If the UPS
input is outside of these ranges, the UPS cannot switch to bypass.
Figure 52: Bypass Setup Page
Press the left or right arrow on the “Bypass Volt Protect Lower Limit” line to adjust the
lower voltage limit from -5% to -25% with a default of -20% on the 1-Phase UPS units,
and adjust the lower limit from -5% to -45% with a default of -20% on the 3-Phase UPS
units.