SMARTZONE UPS USER MANUAL
60
Figure 45: Output Setup Page (3-Phase UPS)
Press the left or right arrow on the Output Frequency (Hz) line to select 50 or 60Hz as
the desired output frequency of the UPS. The default depends on the UPS SKU. EU
UPS units are defaulted to 50Hz, and NA UPS units are defaulted to 60Hz.
Press the left or right arrow on the Output Voltage Level(V) line to select the output
voltage (220, 230, or 240 for EU UPS units and 208 or 240 for NA UPS units). The
default depends on the UPS SKU. EU UPS units are defaulted to 230V, and NA UPS
units are defaulted to 208V.
Press the left or right arrow on the Inverter Volt Adjust (%) line to select from -5% to
+5% (in steps of 0.5%) adjustments to obtain the desired output voltage of the UPS.
The default is set to 0. This adjustment is critical for a Parallel mode system
configuration to ensure optimal load sharing across the UPS units in the system. This
line is not present on the single-phase UPS units.
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the up and over arrow to return to the Advanced Setup Menu page.
Battery Setup Pages
These three pages allow the user to set the system battery parameters of the UPS.
5-10kVA Single-Phase UPS
There are 3 battery setup pages for the 5-10kVA single-phase UPS units.