Switching/Blind Actuator
6
2
Technical Data
KNX Medium
TP1
Mode of commissioning
S-Mode
KNX supply
21-32 V DC
Mains supply
110 / 230 V AC
Mains frequency
50 / 60 Hz
Installation type
DIN rail
Mounting width
12/6 Channels – 144mm (8 modules)
8/4 Channels – 144mm (8 modules)
4/2 Channels– 72mm (4 modules)
Ambient temperature
-5 C …+45 C
Storage temperature
-25 C … +55 C
Transportation temperature
-25 C … +70 C
Connection
KNX
KNX bus terminal
Mains and outputs
Screw terminals
Max. cable cross section
Single wire:
1.5 mm2 to 4mm2 or
2 x 1.5 mm2 to 2x2.5 mm²
Stranded wire without ferrule:
0.75...4 mm²
Stranded wire with ferrule:
0.5mm2 to 2.5mm2
Output contact type
NO ,
potential-
free μ-contact, monostable
Switching Voltage AC
0-230 V
AC
10%,
50/60Hz
Switching capacity at 230V AC
16A cos = 1
3A cos = 0.6
Current load rating per device
4/2 Channels
Sum of C1…C4 maximum 40A
8/4 Channels
Sum of C1…C8 maximum 80A
12/6 Channels
Sum of C1…C12 maximum 120A
Overall load current rating of
neighbouring outputs
Max 20A