4.1.2.3
On/Off Delay Function and Parameters
Basic functionality: If the Function parameter is On/Off Delay, then the channel works for On/Off
delay function. If the channel is switched off and a "1" is sent to the switching object then the switch-
on delay time starts. The switch-on takes place once the switch-on delay time has elapsed. If the
channel is switched on and a "0" is sent to the switching object then the switch-off delay time starts.
The switch-off takes place once the switch-off delay has elapsed. If while a delay time is running the
inverse status is sent then the delay time stops. There is then no switchover. If while a delay time is
running the same status is sent again then this has no effect on the current delay time.
Name
Values
Description
Function
Switch
On/Off Delay
Pulse
Staircase light timer with
prewarning function
This function specifies the function type of the channel. There
are four type of selection function for each channel.
Time base for On/Off
delay
1 sec
10 sec
30 sec
1 min
This parameter defines the time base for switch-off time
delay and switch-on time delay.
The selected value will be multiplied by switch-off time delay
factor and switch-on time delay factor for setting the delay
times.
Factor for switching on
delay (0…255 x timebase)
[0...
5
...255] This parameter defines the switch-on delay time in conjuction
with “Time base for On Off delay” parameter.
Switch-on time delay = time base*factor
Factor for switching off
delay (0…255 x timebase)
[0...
5
...255] This parameter defines the switch-off delay time in
conjuction with “Time base for On Off delay” parameter.
Switch-off time delay = time base*factor
Input logic
None
Or
And
Lock
None:
The channel has the function described at the
beginning.
Or:
If the switching object or linking object is set to "1" then a
switch-on is performed after the switch-on delay time. If both
of objects are set to "0" then a switch-off is performed after
the switch-off delay time.
AND:
If the switching object and the linking object are set to
"1" then the channel is ON after switch-on time delay. If one
of these object is set to “0” then the channel is OFF after
switch-off time delay
.
Lock:
If the linking object is set to "1" the channel is OFF and
then no switch-on is possible via the switching object. If the
linking object is set to "0" then the channel has the function
described at the beginning.