Switching/Blind Actuator
31
4.2.2
Parameters
4.2.2.1
Parameters on “Blind General” Page
Name
Value
Descriptions
Feedback cycle time
2min
3min
5min
10min
15min
20min
30min
45min
60min
This parameter specifies the cycle time of Height and
Slat feedback objects of each channel. The channel
sends its own height and slat level clically to the bus
according to selected value.
Safety status control
Without cyclic monitoring
With cyclic monitoring (10 min.)
With cyclic monitoring (20 min.)
With cyclic monitoring (60 min.)
The actuator monitors whether at least 1 safety
telegram is received within the configured time
period. If the relevant safety telegram fails it adopts
the safety status.
The monitoring time is set to twice the value of the
send time of the safety telegrams. The objects are
monitored independently of each other. The
monitoring time applies to all 3 objects.
Blind Slat 0% position
assignment
0% position for lowering
0% position for ascending
Input of the starting position for the calculations of
the slat turn.
Use manual control
buttons
No
Yes
The manual control with keypad is enabled or
disabled with this parameter.
Delay at inversion of
direction
0.5 sec.
1.25 sec.
This parameter defines the pause time required at
inversion of direction. This setting depends on the
information supplied by the manufacturer of the
drive.