Solar Three-way Valve
Cable (Optional)
External Control Cable
(Optional)
Tank Sensor Cable
(Optional)
Tank OLP Cable (Optional)
Detail A
Solar Pump Station Cable
(Optional)
Three-way Valve Cable
(Optional)
Two-way Valve Cable
(Optional)
Earth wire must be longer
than other cables for safety
reasons.
Room Thermostat Cable
(Optional)
Booster Heater Cord
(Optional)
12.3.4.1 Wire Stripping and Connecting Requirement
-30
-10
0
10
20
30
-20
16000
14000
12000
10000
8000
˚
C
6000
4000
2000
0
Graph 5.1: Tank sensor characteristic
Tank Sensor Resistance Vs Temperature
Re
sist
a
n
ce
(
k
Ω
)
Wire stripping
5mm or
more
(gap between
wires)
No loose strand
when insert
Indoor/outdoor
connecting
terminal board
10
±
1mm
ACCEPT
PROHIBITED
Conductor
over insert
Conductor not
fully insert
Conductor
fully insert
PROHIBITED
17
18
Diagram 5.2: External Controller connecting
diagram
External Controller
Terminal
Switch (ON/OFF)
Remove this
jumper if External
Controller
(Optional) is
connected to the
indoor unit
12.3.4.2 Connecting
Requirement
The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S
sc
is
greater than or equal to 1200 kW (for WH-SDC14/16F6E5/UD14/16FE5) at the interface point between the user’s
supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the equipment is connected only to a supply
with a short-circuit power S
sc
greater than or equal to 1200 kW.
The equipment's power supply 1 shall be connected to a suitable supply network, having service current capacity
≥
100A per phase. Please liaise with supply authority to ensure that the service current capacity at the interface
point is sufficient for the installation of the equipment.
The equipment’s power supply 2 complies with IEC/EN 61000-3-12.
The equipment’s power supply 2 shall be connected to a suitable supply network, with the following maximum
permissible system impedance Z
max
at the interface of the point: 0.271
Ω
. Please liaise with supply authority to
ensure that power supply 2 is connected to a supply of the impedance or less.