17.5.9 Deice Circulation Error (H65)
Malfunction Decision Conditions:
During startup and operation of deice (mode 2), the water flow (> 10l/min) detected by the water flow switch is
used to determine deice circulation error.
Malfunction Caused:
1 Water flow in air-to-water heatpump indoor unit circuitry.
2 Faulty indoor unit water flow switch.
3 Faulty indoor unit water pump.
4 Faulty indoor unit PCB.
Abnormality Judgment:
Continue for 10 seconds.