61
13.1.4 Auto Mode Operation
Outdoor Ambient
Cool To Heat
Setting Temp.
COOL
MODE
HEAT
MODE
Heat To Cool
Setting Temp.
Control
details:
o
To enable the unit to operate either heat or cool mode automatically, heat to cool set temperature and
cool to heat set temperature can be set by control panel.
o
Automatic operation is judged based on control panel setting temperature and outdoor ambient
temperature.
* Minimum setting of heat to cool set temperature is 1°C higher than cool to heat set temperature.
Judgement
control:
o
If outdoor ambient temperature < Heat to Cool Set Temperature, unit will operate in Heat Mode or else
the unit will operate in Cool Mode.
o
If current operation is Cool mode, outdoor ambient temperature > Cool to Heat Temperature, unit will
maintain Cool mode operation or else the unit will operate Heat mode.
o
If current operation is Heat mode, outdoor ambient temperature >Heat to Cool Temperature, unit will
maintain Heat mode operation or else the unit will operate Cool mode.
o
Every 60 minutes the outdoor ambient temperature is judged.
o
When Auto + Tank mode is selected, operation mode switching is judged by both outdoor ambient
temperature and indoor air temperature.