146
17.5.37
Cooling High Pressure Overload Protection (F95)
Malfunction Decision Conditions:
During operation of cooling, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor.
Malfunction Caused:
1 Dust accumulation in the outdoor unit heat exchanger.
2 Air short circuit at outdoor unit.
3 2 way valve closed.
4 Faulty outdoor unit fan motor.
5 Clogged expansion valve or strainer.
6 Excessive
refrigerant.
7 Faulty outdoor high pressure sensor.
8 Faulty outdoor unit PCB (main).
Содержание WH-SDC12F6E5
Страница 24: ...24 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 63: ...63 57 C 57 C 57 C 57 C ...
Страница 64: ...64 ...
Страница 70: ...70 ...
Страница 71: ...71 ...
Страница 72: ...72 57 C 57 C 50 C 50 C ...