77
13.1.8 Setting Water Outlet Temperature for Heat Mode
The set temperature defines the parameters for the outdoor ambient temperature dependent operation of the
unit. Where by the internal water setting temperature is determined automatically depending on the outdoor
temperature. The colder outdoor temperatures will result in warmer water and vice versa. The user has the
possibility to shift up or down the target water temperature by control panel setting.
Outdoor
Temp.
Water
Temp.
H2O HI
H2O LO
OUT LO
OUT HI
outdoor ambient set temperature
outdoor ambient set temperature
OUT LO = Low outdoor ambient set temperature
OUT HI = High outdoor ambient set temperature
H2O LO = Water outlet set temperature at low
H2O HI = Water outlet set temperature at high
Outdoor temperature is updated every 30 minutes when operation ON.
Setting water outlet temperature always follow H20 (Lo) or H2O (Hi) whenever is higher if outdoor ambient
sensor or indoor communication error happen.
Operation under tank mode
When heat pump operate to tank side, the water outlet target temperature is 53°C.