** However indoor water pump can operate when Anti-freeze control condition fulfilled.
o
Boiler signal turn OFF and heat pump and water pump turn ON when:
Outdoor ambient > Outdoor Ambient Set + [2°C]
OR
Boiler prohibit flag = 1
Parallel Mode
o
Parallel mode allows heat pump and boiler ON at the same time. Boiler operates as an additional heating
capacity when low heat pump capacity at low ambient condition.
Control detail:
During operation ON at Heat mode or Tank mode or Heat + Tank mode
o
Boiler signal turns ON when:
Outdoor ambient < Outdoor Ambient Set
AND
Boiler prohibit flag = 0
o
Boiler signal turns OFF when:
Outdoor ambient > Outdoor Ambient Set + [2°C]
OR
Boiler prohibit flag = 1
Advance Parallel Mode
o
Advance parallel mode allow heat pump to operate and turn ON boiler only when ambient and temperature
condition is fulfilled.
Remote control setting value:
1 Outdoor Ambient Set = (Range : -15°C ~ 15°C)
2 Selection of boiler connection direction. (Heat only, DHW only, Heat & DHW)
3 Setting data under Heat Direction
o
Start Temperature | START_TEMP |
o
Start Delay Timer | START_TIMER |
o
Stop Temperature | STOP_TEMP |
o
Stop Delay Timer | STOP_TIMER |
4 Setting data under DHW Direction
o
Delay Timer
| DELAY_TIMER |
Control detail:
During operation ON at Heat Mode
o
Boiler signal turns ON when
Outdoor ambient < Outdoor Ambient Set
AND
Buffer tank temperature < Target Buffer Tank Tempe [START_TEMP] for [START_TIMER]
AND
Heat pump operate at room side
AND
Connection of Boiler to Heating Select "YES" From installer menu
AND
Buffer Tank connection select "YES"
AND
Boiler prohibit flag = 0
o
Boiler signal turns OFF when
Outdoor ambient > Outdoor Ambient Set + [-2°C]
OR
Buffer Tank temperature > Target Buffer Tank tempe [STOP_TEMP] for [STOP_TIMER]
OR
Heat pump not at room side.
OR]
Boiler prohibit flag = 1
During operation ON at Tank Mode
o
Boiler signal turns ON when
Outdoor ambient < Outdoor Ambient Set
AND
Heat pump operate at tank side for continuous | DELAY_TIMER |
AND
Connection of Boiler to DWH Tank select "YES" from installer menu.
AND
Boiler prohibit flag = 0
o
Boiler signal turns OFF when
Outdoor ambient > Outdoor Ambient Set + [2°C]
OR
Heat pump not operates at tank side.
OR
Boiler prohibit flag = 1