17
4. Features
Inverter Technology
- Energy saving
High Efficiency
Compact Design
Environment Protection
- Non-ozone depletion substances refrigerant (R32)
Easy to use control panel
Weekly Timer setting
Quality Improvement
- Random auto restart after power failure for safety restart operation
- Gas leakage protection
- Prevent compressor reverse cycle
- Inner protector to protect compressor
Serviceability Improvement
- Breakdown Self Diagnosis function
- System Status Check Buttons for servicing purpose
- System Pumpdown Button for servicing purpose
- Front maintenance design for outdoor unit
Operation Condition
HEATING (CIRCUIT)
*
1,
*
2
COOLING (CIRCUIT)
Water outlet temperature (°C)
(Min. / Max.)
20 / 55 (Below Ambient -20°C) *
3
20 / 60 (Ambient -15 ~ 0°C or
Above Ambient 25°C) *
3
20 / 65 (Ambient 5 ~ 20°C) *
3
*
4
5 / 20
Outdoor ambient temperature (°C)
(Min. / Max.)
-20 / 35
10 / 43
When the outdoor temperature is out of the range in the table, the heating capacity will drop significantly and the
mono bloc unit may stop operating for its protection.
The unit will restart automatically after the outdoor temperature returns to the specified range.
*
3
Between outdoor ambient -15°C and -20°C, the water outlet temperature gradually decreases from 60°C to 55°C.
*
3
Between outdoor ambient 5°C and 0°C, the water outlet temperature gradually decreases from 65°C to 60°C.
*
3
Between outdoor ambient 20°C and 25°C, the water outlet temperature gradually decreases from 65°C to 60°C.
*
4
Only when ΔT is set to 15
°
C, the set temperature above 60
°
C will take effect.