67
Floor h Radiator
Radiator
Thermistor 1
Thermistor 2
Buffer tank
Pump 2
Pump 1
Mixing valve 1
Mono bloc
Floor heating
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Water temperature
Zone 2:Sensor
Room
Water temperature
Connect floor heating or radiator to 2 circuits through buffer tank as shown in figure.
Install pumps and thermistors (specified by Panasonic) on both circuits.
Install mixing valve in the circuit with lower temperature among the 2 circuits.
(Generally, if install floor heating and radiator circuit at 2 zones, install mixing valve in floor heating circuit.)
For temperature setting, select circulation water temperature for both circuits.
Both circuits can set circulation water temperature independently.
Install buffer tank thermistor on buffer tank.
It requires connection setting of buffer tank and ∆T temperature setting at heating operation separately.
This system requires the optional PCB (CZ-NS4P).
Mind that if there is no mixing valve at the secondary side, the circulation water temperature may get higher than
setting temperature.
Floor h Swimming pool
Thermistor 1
Heat EX
Thermistor 3
Thermistor 2
Buffer tank
Pump 2
Pump 3
Pump 1
Mixing
valve 1
Mixing
valve 2
Mono bloc
Floor heating 1
Swimming pool
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Room thermostat
Internal
Zone 2
Swimming pool
T
Connect floor heating and swimming pool to 2 circuits through buffer tank as shown in figure.
Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits.
Then, install additional pool heat exchanger, pool pump and pool sensor on pool circuit.
Install the remote controller in room where floor heating is installed. Circulation water temperature of floor heating
and swimming pool can be set independently.
Install buffer tank sensor on buffer tank.
It requires connection setting of buffer tank and ∆T temperature setting at heating operation separately. This system
requires the optional PCB (CZ-NS4P).
Must connect swimming pool to “Zone 2”.
If it is connected to swimming pool, operation of pool will stop when “Cooling” is operated.