12.1.5 Installation of Remote Controller
12.1.5.1 Installation
Location
Install at the height of 1 to 1.5 m from the floor (Location where average room temperature can be detected).
Install vertically against the wall.
Avoid the following locations for installation.
1 By the window, etc. exposed to direct sunlight or direct air.
2 In the shadow or backside of objects deviated from the room airflow.
3 Location where condensation occurs (The Remote Controller is not moisture proof or drip proof.)
4 Location near heat source.
5 Uneven surface.
Keep distance of 1 m or more from the TV, radio and PC. (Cause of fuzzy image or noise)
12.1.5.2 Remote
Controller
□
3
Wiring
1
2
Terminal for Remote Controller wiring
Remote Controller
Mono bloc unit
Remote Controller
wiring (field supply)
•
No polarity
Remote Controller cable shall be (2 x min 0.3 mm
2
), of double insulation PVC-sheathed or rubber sheathed cable.
Total cable length shall be 50 m or less.
Be careful not to connect cables to other terminals (e.g. power source wiring terminal). Malfunction may occur.
Do not bundle together with the power source wiring or store in the same metal tube. Operation error may occur.
12.1.5.3 Mounting
The
Remote Controller
For exposed type
Preparation:
Make 2 holes for screws using a driver.
UP
Cut here with
a nipper and
remove the burr
with a file.
Mount the top case.
•
Align the claws of the top
case and then align the claws
of the bottom case.
Hole for screw
Screw
(field supply)
Claw (2 places)
Pass through
the hole
Bottom case
(Back side)
Top case
(Back side)
Remote controller terminal board
Remove the coating. Approx. 6 mm
Remove the sheath. Approx. 180 mm.
Make sure the wiring connection is in the
correct direction.
Clamper
(field supply)
Claw (2 places)
Wall to which
the remote
controller is
fixed
Mount the bottom case to
the wall.
Connect the remote control
wiring
•
Arrange the wires along the groove
of the case.