207
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Appendix
8
24
Menus
For installer
Menu
Default Setting
Setting Options / Display
5 Installer setup System setup
5.1
Optional PCB connectivity
To connect to the external PCB
required for servicing�
No
•
If the external PCB is connected (optional), the system will have following additional functions:
1
Buffer tank connection and control over its function and temperature�
2
Control over 2 zones (including the swimming pool and the function to heat water in it)�
3
Solar function (the solar thermal panels connected to either the DHW (Domestic Hot Water) Tank or the Buffer Tank�
•
DHW is not applicable for WH-ADC
*
models�
4
External compressor switch�
5
External error signal�
6
SG ready control�
7
Demand control�
8
Heat-Cool SW
5.2
Zone & Sensor
To select the sensors and to
select either 1 zone or 2 zone
system�
Zone
•
After selecting 1 or 2 zone system, proceed
to the selection of room or swimming pool�
•
If the swimming pool is selected, the
temperature must be selected for
T temperature between 0°C ~ 10 °C�
Sensor
* For room thermostat, there is a further
selection of external or internal�
5.3
Heater capacity
To reduce the heater power if
unnecessary�*
3 kW / 6 kW / 9kW
* Options of kW vary depending
on the model�
5.4
Anti freezing
To activate or deactivate the
water freeze prevention when
the system is OFF
Yes
5.5
DHW capacity
To select tank heating capacity
to variable or standard� Variable
capacity heat up tank with
fast mode and keep the tank
temperature with efficient mode.
While standard capacity heat up
tank with rated heating capacity�
Variable