8
Open the ceiling board along the
outer edge of the paper model.
Adjust to the same
height
Ceiling
Air conditioner
body
Paper model for
installation
Set screw for paper
model (4 pieces)
283 mm
293 mm
and above
Keep the length of the bolt
from the bracket to 40 mm
Fig. 3-3
WARNING
Tighten the nut and bolt to prevent unit from falling.
3-4. Installing the Drain Pipe
Heat insulator (Local
supply) (The thickness
must be at least 8 mm.)
Flexible hose with
heat insulator
(Accessory)
Hose clip (Accessory)
PVC pipe
(O.D. ø32)
(Local supply)
To be glued
It may be required to take off this part for checking or
servicing the drain up motor. Please do not glue.
Make sure that there is no clearance here.
Fig. 3-4
N OT E
Make sure the drain pipe has a downward gradient (1/100 or
more) and that there are no water traps.
3-5. Indoor Unit Drain Piping
●
During drain piping connection, be careful not to exert extra
force on the drain port at the indoor unit.
●
The outside diameter of the drain connection at the indoor
unit is 32 mm.
Piping material: Polyvinyl chloride pipe VP-25 and pipe
fittings.
●
Be sure to perform heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thickness
more than 8 mm (local supply).
●
Drain piping must have down-slope (1/50 to 1/100); be sure
not to provide up-and-down slope to prevent reversal flow.
●
Be sure to check no air trap on drain hose and to ensure
smooth water flow and no abnormal sound.
Upward routing
Indoor
unit
Pipe clamp
Down-slope
Trap
Fig. 3-5
Down-slope
Upward-slope
No Air Trap
Air Trap
Fig. 3-6
●
The height of drain may be possible up to 750 mm.
Drain port
Indoor unit
750 mm or less
Down-slope (1/50 ~ 1/100)
Elbow
Elbow
Fig. 3-7
●
When drain set piping, install as shown in the figure below.
Use VP30 or more for confluence
Indoor
unit
Down-slope (1/50 ~ 1/100)
Apply the head when connecting with the
confluence pipe. (about 100 mm)
Fig. 3-8
Drain Test
The air conditioner uses a drain up motor to drain water. Use
the following procedure to test the drain up motor operation.
●
Connect the main drain pipe to exterior and leave it
provisionally until the test comes to an end.
●
Feed water to the flexible drain hose and check the piping for
leakage.
●
Be sure to check the drain up motor for normal operating and
noise when electric wiring is complete.
●
When the test is complete, connect the flexible drain hose to
the drain port.
Drain hose connection
Use the clip (accessory)
Feed water
Drain up motor
Drain hose
Main drain pipe
Glue the joint
Drain
port
Fig. 3-9