46
Case 1
Auto Address Control from Outdoor Unit
1. Regarding the number of outdoor units, set the Dip switch (SW6) for setting the number of outdoor units on Unit 1 control P.C.B to 3
units
1
2 3
ON
ON
OFF
and the Unit Number Setting Dip switch (SW5) to unit number 1.
2 3
1
ON
This unit becomes the outdoor main unit.
2. Set the Unit Number Setting switch (SW5) on unit 2 control P.C. board to unit number 2.
3
2
1
ON
Set the Unit Number Setting switch (SW5) on unit 3 control P.C. board to unit number 3.
3
2
1
ON
3. Check the refrigerant system's Address Setting Rotary switch (SW1) on outdoor main unit control P.C. board to “1” and the Dip switch
(SW2) to “0” (at shipment).
1
2
ON
ON
OFF
4. Regarding the setting of the number of indoor units connected to the outdoor unit, set the Dip switch (SW4) for setting the number of
indoor units on outdoor main unit control P.C. board connected to the outdoor unit to “1”.
2 3
1
ON
ON
OFF
If the Rotary switch (SW3) set to “0”, 10 units can be prepared for operation.
5. Turn on power to indoor and outdoor units.
6. Short circuit the A.ADD pin (CN30) on outdoor main unit control P.C. board for over 1 second long and open circuit.
Communication for auto address setting begins.
* To cancel, short circuit the A.ADD pin (CN30) again for over 1 second long and then open circuit. The LED that
indicates auto address setting goes out and the process is stopped.
Be sure to perform auto address setting again.
Auto address setting is completed when LEDs 1 and 2 on outdoor main unit control P.C. board go out.
7. Remote control operation is now available.
* When auto address setting is controlled by the remote controller, perform auto address setting by the remote controller after step 5
described above.
●
See to section “Auto Address Setting from Remote Controller”.
7-5. Auto Address Setting
Example: Basic Wiring Diagram (1)
• Case of no link wiring
(Inter-unit control wiring is not connected to a multiple system.)
Indoor unit address setting is possible without starting the compressor.
1
2 3
3
2
1
1
3
2
1 2
2
1
3
3
2
1
0
1
1-1
1-2
1-3
1-10
Unit 1 setting (outdoor main unit)
Unit 2 setting
Unit 3 setting
3P terminating
resistance pin
(SHORT side)
No. of indoor units
(10 units setting)
System address
(System 1 setting)
(SW1)
(SW3)
(SW4)
(SW5)
(SW5)
(SW5)
Unit 3
(Sub)
Inter-outdoor unit
control wiring
Remote control
communication wiring
Inter-unit control wiring
Outdoor Unit
Indoor unit
Remote controller
Set the terminating
resistance pin
to SHORT side.
(CN67)
Inter-outdoor unit
control wiring
Unit 2
(Sub)
Unit 1
(Main)
OPEN
SHORT
(SW6)
(SW2)
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
Unit
number
setting
(unit 1)
Unit
number
setting
(unit 2)
Unit
number
setting
(unit 3)
Number of
outdoor units
(3 units setting)
* It is not necessary to control the terminating
resistance pin (3P) (CN67) on the outdoor unit
P.C. board.
3P pin is plugged in SHORT side at shipment.
Confirm it is plugged in SHORT side.
00_302411_EN.indd 46
2018/7/4 13:27:58
Содержание U-120ME2U9
Страница 61: ...61 NOTE 00_302411_EN indd 61 2018 7 4 13 28 03 ...
Страница 62: ...62 NOTE 00_302411_EN indd 62 2018 7 4 13 28 03 ...
Страница 63: ...63 NOTE 00_302411_EN indd 63 2018 7 4 13 28 03 ...
Страница 64: ...ACXF60 18511 DC0314 30718 Printed in China 85464369760022 00_302411_EN indd 64 2018 7 4 13 28 04 ...