9
1-6. Tubing Size
Table 1-3 Main Tubing Size (LA)
Between No.1 distribution joint for outdoor unit and No.1 distribution joint (for indoor unit)
Unit: in. (mm)
BTU/h
(kW)
72,000
(21.1)
96,000
(28.1)
120,000
(35.2)
144,000
(42.2)
168,000
(49.2)
192,000
(56.3)
216,000
(63.3)
240,000
(70.3)
264,000
(77.4)
288,000
(84.4)
312,000
(91.4)
336,000
(98.4)
360,000
(105.5)
Total system
tonnage
6
8
10
12
14
16
18
20
22
24
26
28
30
Gas tubing
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.92)
ø1-5/8"
(ø41.28)
Liquid tubing
ø3/8"
(ø9.52)
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
*1: If future extension is planned, select the tubing diameter based on the total tonnage after extension.
However, extension is not possible if the resulting tubing size is three ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø1/4" (6.35mm).
*3: Type 1 tubing should be used for the refrigerant tubes.
n
Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 1-4 Main Tubing Size After Distribution (LB, LC...)
Unit: in. (mm)
Total capacity
after distribution
Below BTU/h (kW)
24,200
(7.09)
54,600
(16.0)
76,800
(22.5)
102,400
(30.0)
143,300
(42.0)
178,800
(52.4)
238,900
(70.0)
340,000
(99.6)
–
Over BTU/h (kW)
–
24,200
(7.09)
54,600
(16.0)
76,800
(22.5)
102,400
(30.0)
143,300
(42.0)
178,800
(52.4)
238,900
(70.0)
340,000
(99.6)
Tubing size
Gas tubing
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.92)
ø1-5/8"
(ø41.28)
Liquid tubing
ø3/8"
(ø9.52)
ø3/8"
(ø9.52)
ø3/8"
(ø9.52)
ø3/8"
(ø9.52)
ø1/2"
(ø12.7)
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø3/4"
(ø19.05)
Note:
In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing size
for the total capacity of the outdoor units.
Table 1-5 Outdoor Unit Tubing Connection Size (
A
–
C
)
Unit: in. (mm)
BTU/h
(kW)
72,000
(21.1)
96,000
(28.1)
120,000
(35.2)
144,000
(42.2)
Gas tubing
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
Brazing connection
Liquid tubing
ø3/8" (ø9.52)
ø3/8" (ø9.52)
ø1/2" (ø12.7)
Flare connection
Balance tubing
ø1/4" (ø6.35)
Flare connection
Table 1-6 Refrigerant Charge Amount at Shipment (for outdoor unit)
BTU/h (kW)
72,000 (21.1)
96,000 (28.1)
120,000 (35.2) 144,000 (42.2)
Initial amount
oz (
g
)
321 (9,100)
363 (10,300)
300 (8,500)
416 (11,800)
Table 1-7 Indoor Unit Tubing Connection Size
Unit: in. (mm)
Indoor unit type
7
9
12
15
18
24
36
48
54
Gas tubing
ø1/2" (ø12.7)
ø5/8" (ø15.88)
Liquid tubing
ø1/4" (ø6.35)
ø3/8" (ø9.52)
ex.) type72
Balance
tube
Liquid tube
Gas tube
00_302411_EN.indd 9
2018/7/4 13:27:17
Содержание U-120ME2U9
Страница 61: ...61 NOTE 00_302411_EN indd 61 2018 7 4 13 28 03 ...
Страница 62: ...62 NOTE 00_302411_EN indd 62 2018 7 4 13 28 03 ...
Страница 63: ...63 NOTE 00_302411_EN indd 63 2018 7 4 13 28 03 ...
Страница 64: ...ACXF60 18511 DC0314 30718 Printed in China 85464369760022 00_302411_EN indd 64 2018 7 4 13 28 04 ...