14
3. CZ-P160BK1U Use: For indoor unit (Capacity after distribution joint is 76,400 BTU/h (22.4 kW) or less.)*
4-21/64
(110)
4-21/64
(110)
(97)
3-13/16
3-13/16
(97)
2-53/64
(72)
2-53/64
(72)
B
A
D
B
B
C
C
C
D E
A
C
D
E
C
Example:
Gas tubing
Liquid tubing
Distribution
Joint
Distribution
Joint
Insulation
Insulation
Unit: in. (mm)
Table 1-15 Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
Part B
Part C
Part D
Part E
in. (mm)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
ø1/4"
(ø6.35)
4. CZ-P680BK1U Use: For indoor unit (Capacity after distribution joint is greater than 76,400 BTU/h (22.4 kW) and no
more
than 232,000 BTU/h (68.0 kW).
)*
6-57/64
(175)
5-5/16
(135)
4-21/64
(110)
(97)
3-13/16
E
E
F
G
F
G
H
B
C
D
E
F
E
B C D
F G H
D C B
E F
4-31/64
(114
)
2-53/64
(72)
A
A
A
Example:
Gas tubing
Liquid tubing
Distribution
Joint
Distribution
Joint
Insulation
Insulation
Reducing
Joints
Reducing
Joints
Unit: in. (mm)
Table 1-16 Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
Part B
Part C
Part D
Part E
Part F
Part G
Part H
in. (mm)
ø1-1/8"
(ø28.58)
ø1"
(ø25.4)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
ø1/4"
(ø6.35)
5. CZ-P1350BK1U Use: For indoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW).)*
(175)
(135)
4-21/64
(110)
(97)
3-13/16
4-31/64
(114)
2-53/64
(72)
6-57/64
5-5/16
H
I
J
C
D
E
F
G
H
G
F
F
H
G
G
B
C
D
B
B
A
C D
A
A
Unit: in. (mm)
Gas tubing
Liquid tubing
Example:
Distribution
Joint
Distribution
Joint
Insulation
Insulation
Reducing
Joints
Reducing
Joints
: Outside dimension
*
With regard to the diameter of the tube without description in Table 1-17, use a reducer (field supply) to adjust the tube diameter.
Table 1-17 Size of connection point on each part (Shown are inside diameters of tubing)
Size
Part A
Part B
Part C
Part D
Part E
Part F
Part G
Part H
Part I
Part J
in. (mm)
ø1-3/8"
(ø34.92)
ø1-1/4"
(ø31.75)
ø1-1/8"
(ø28.58)
ø1"
(ø25.4)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
ø1/4"
(ø6.35)
In case the total capacity of indoor units connected after distribution exceeds the total capacity of the outdoor units, select the
distribution tube size for the total capacity of the outdoor units.
00_302411_EN.indd 14