3. HOW TO INSTALL THE OUTDOOR UNIT
3-1. Transporting
When transporting the unit, have it delivered as close to the installation site as
possible without unpacking. Use a hook for suspending the unit.
CAUTION
CAUTION
●
When hoisting the outdoor unit, pass ropes or straps under the bottom plate
as shown in the figure at right. When hoisting, the angle between the rope
and top panel must be 70° or greater so that the rope does not come into
contact with the fan guard.
(Use 2 lengths of rope 25 ft. (approx. 7.6 m) long or more.)
●
When passing the ropes through the square holes of the bottom plate:
Place the rope in the outer edge of the square holes.
●
Use protective panels or padding at all locations where the rope
contacts the outer casing or other parts to prevent scratching.
In particular, use protective material (such as cloth or cardboard)
to prevent the edges of the top panel from being scratched.
●
Be careful of the fan.
There is danger of injury if the fan starts to turn during inspection.
Be sure to turn OFF the remote power switch before beginning
inspection.
3-2. Installing the Outdoor Unit
(1) Use anchor bolts (15/32" or M12) or similar to securely anchor the unit in place.
(2) Make sure the rubber vibration insulator and platform extend to the inside of the legs. In addition, the washers used to anchor the
unit from the top must be larger than the installation anchor holes.
A:
37-61/64
(964)
B: 28-47/64 (730
)
C: 28-47/64 (730
)
F
D
D
D
D
D
D
E
E
D
H
D
D
E
E
G
Type 120/144
Vibration insulator
Vibration insulator
Vibration insulator
Unit: in. (mm)
(Installation hole pitch)
(Installation hole pitch)
(Installation hole pitch)
<Detailed view of legs>
2 support area per each leg (x2) must install vibration insulator material and mount.
The area of dimension marked with the asterisk (*) must cover the base.
<Detailed view of installation holes>
4” (100
)
4” (100
)
4” (100
)
19-32 (15)
*2-51/64 (71)
*3-15/16 (100)
*3-15/16 (100)
Unit: in. (mm)
Leg
Leg
Anchor bolt
Anchor bolt
Anchor bolt
Washer
Washer
Washer
Vibration insulator
Vibration insulator
Vibration insulator
Base
Base
Base
Ov
er
Ov
er
View F (area D/E)
View G (area D)
View H (area E)
Unit: in. (mm)
(19/32 (15) x 53/64(21))
45/64 (18)
19/32 (15)
9-59/64 (252
)
Unit: in. (mm)
Installation elongated hole
A
A
Detailed
drawing A
This is not a lifting lug.
<Do not attempt to lift the unit by one of the
legs at each corner of the unit or with hooks
or shackles attached for installing the legs.>
Rope
00_302411_EN.indd 23
2018/7/4 13:27:42
Содержание U-120ME2U9
Страница 61: ...61 NOTE 00_302411_EN indd 61 2018 7 4 13 28 03 ...
Страница 62: ...62 NOTE 00_302411_EN indd 62 2018 7 4 13 28 03 ...
Страница 63: ...63 NOTE 00_302411_EN indd 63 2018 7 4 13 28 03 ...
Страница 64: ...ACXF60 18511 DC0314 30718 Printed in China 85464369760022 00_302411_EN indd 64 2018 7 4 13 28 04 ...