26
Refrigerant tube port
●
Use caulking, putty, or a similar material to fill any gaps at the
refrigerant tube port (
) in order to prevent rainwater, dust or
foreign substances from entering the unit.
* Perform this work even if the tubing is routed out in a downward
direction.
●
Tighten each cap as specified below.
Tightening torque for each cap
Cap tightening torque
Width
unit: lbs · inch
unit: N · m
unit: {k
g
f · cm}
Service port cap
43/64" (17mm)
90 - 100
10 - 12
{100 - 120}
Valve cap
35/64" (14mm),
43/64" (17 mm)
170 - 220
20 - 25
{200 - 250}
3/4" (19 mm)
120 - 170
14 - 20
{140 - 200}
17/16" (27mm)
190 - 240
22 - 28
{220 - 280}
Tubing cover
Tubing routed out
through the front side
Bottom plate
Tubing routed out
through the bottom
For type 72
Service port cap
width 43/64 (17)
Valve cap
width 3/4 (19)
Valve cap
width 35/64 (14)
Valve cap
width 35/64 (14)
Service port cap
width 43/64 (17)
Service port cap
width 43/64 (17)
Flare nut
ø1/4 (6.35)
Flare nut
ø3/8 (9.52)
For type 120/144
Service port cap
width 43/64 (17)
Valve cap
width 17/16 (27)
Valve cap
width 35/64 (14)
Valve cap
width 43/64 (17)
Service port cap
width 43/64 (17)
Service port cap
width 43/64 (17)
Flare nut
ø1/4 (6.35)
Flare nut
ø1/2 (12.7)
For type 96
Unit: in. (mm)
Service port cap
width 43/64 (17)
Valve cap
width 3/4 (19)
Valve cap
width 35/64 (14)
Valve cap
width 43/64 (17)
Service port cap
width 43/64 (17)
Service port cap
width 43/64 (17)
Flare nut
ø1/4 (6.35)
Flare nut
ø3/8 (9.52)
Do not apply an adjustable wrench
to the hexagonal part.
Use two adjustable wrenches, as shown in the figure,
when removing the liquid tube valve flare nut.
Do not use two adjustable wrenches when removing or
installing the balance tube flare nut. In particular, do not
apply an adjustable wrench to the hexagonal part at the top
of the valve. (If force is applied to this part, gas leakage will
occur.)
1. Do not apply a wrench to the valve cap when
removing or installing the flare nuts.
Doing so may damage the valve.
2. If the valve cap is left off for a long period of time,
refrigerant leakage will occur.
Therefore, do not leave the valve cap off.
3. Applying refrigerant oil to the flare surface can be
effective in preventing gas leakage, however be
sure to use a refrigerant oil which is suitable for
the refrigerant that is used in the system. (This unit
utilizes R410A refrigerant, and the refrigerant oil is
ether oil (synthetic oil).
However, hub oil (synthetic oil) can also be used.)
00_302411_EN.indd 26
2018/7/4 13:27:45
Содержание U-120ME2U9
Страница 61: ...61 NOTE 00_302411_EN indd 61 2018 7 4 13 28 03 ...
Страница 62: ...62 NOTE 00_302411_EN indd 62 2018 7 4 13 28 03 ...
Страница 63: ...63 NOTE 00_302411_EN indd 63 2018 7 4 13 28 03 ...
Страница 64: ...ACXF60 18511 DC0314 30718 Printed in China 85464369760022 00_302411_EN indd 64 2018 7 4 13 28 04 ...