SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
WUME-SCHG1IQRFB-1
56/184
Error code
■ List of error codes
Error code
(hexadecimal)
Description
Meaning
100
The Station No. (i_uStationNo) is
outside the valid range
For CC-Link master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 64.
For CC-Link IE Field master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 120.
101
The information derived from the input
Start I/O No.(i_uStartIONo) and the
Station No. (i_uStationNo) is not
SC-HG1-C or SC-HG1-CEF.
Check if the Start I/O No.(i_uStartIONo) and the Station No.
(i_uStationNo) settings correctly indicate the target
communication unit.
104
Set to a controller where Set Controller
(i_uSetController) is set to 0 or does
not exist
Make the value of Set Controller (i_uSetController) greater
than 0.
Check if the setting is not applied to a controller beyond the
maximum number of connected units. Also, check if the 15th
bit of Set Controller (i_uSetController) is not ON.
109
Hold Setting (i_uHoldSetting) is
outside the valid range
Specify a value within the valid range.
10A
Self Trigger Level
(i_dSelfTriggerLevel) is outside the
valid range
Specify a value from -1999999 to 1999999.
10B
Static Span (i_udStaticSpan) is outside
the valid range
Specify a value from 0 to 1999999.
10C
Self Delay Timer (i_uSelfDelayTimer)
is outside the valid range
Specify a value from 0 to 9999.